Siemens Welding System ST PCS 7 Manual De Usuario

Descargar
Página de 344
Asset Management
 
Maintenance station
8/4
Siemens ST PCS 7 · November 2007
8
Function
Diagnostics message of a component in the faceplate view "Identity"
The maintenance station provides comprehensive maintenance 
information for the system components of the plant (assets). In 
order to obtain information on the diagnostics status of individual 
plant areas or components, maintenance engineers can change 
from the overview display to the respective diagnostics display 
of the subordinate hardware level. If a fault is signaled in the 
overview display, the "loop in alarm" function permits rapid 
switching to the diagnostics faceplate of the associated compo-
nent.
The scope of information available depends on the individual 
possibilities of the asset, and is filtered according to the user’s 
area of responsibility.
The following information is available:
• Display of diagnostics status determined by the system
• Information on components such as tag name, vendor or se-
rial number
• Display of diagnostics messages of a component
• Visualization of type and current state of initiated maintenance 
measure
Information on passive or indirect assets
For passive or indirect assets (pumps, motors, control loops 
etc.) without self-diagnostics, you can use the programmable 
logic block AssetMon to derive inadmissible operating states 
from various measured values and their deviations from a de-
fined normal status and to display them as a maintenance alarm 
on the maintenance station. AssetMon is able to process up to 
3 analog values and up to 16 binary values.
With the aid of the AssetMon, individual diagnostics structures, 
project-specific diagnostics rules and condition monitoring 
functions can also be implemented.
Enhanced information for assets according to IEC 61804-2
Further information can be called for assets described by the 
electronic device description (EDD) according to IEC 61804-2. 
This information is automatically read out of the components and 
made available by SIMATIC PDM in the background.
• Detailed diagnostics information 
- Device-specific information from the vendor
- Information on fault diagnostics and troubleshooting
- Additional documentation
• Results of internal condition monitoring functions
• Status information (e.g. local operation, local configuration 
changes)
• Display of modification logbook (audit trail) of the component 
with all entries on the persons, times and types of operator in-
tervention on the component
• Parameter view of the assets (display of parameters saved in 
the component and in the project; if required, also differences 
between them)
Uniform symbols
Uniform symbols for visualization of the maintenance status and for HMI 
on the maintenance station
A significant feature with visualization of the access manage-
ment functionality is the uniform symbols and texts for displaying 
the statuses of all assets, i.e. for operator stations as well as for 
network components, controllers or field devices. The asset 
faceplates are also uniform. The amount of information dis-
played depends on the intelligence of the respective compo-
nent.
Gut 
Simulation 
Konfigura- 
tionsände- 
rung erkannt 
Wartungs- 
bedarf 
(gering) 
Wartungs- 
anforderung 
(mittel) 
Wartungs- 
alarm 
(hoch) 
Instandhaltungs- 
Auftrag unbek./ 
nicht angefordert 
Instandhaltungs- 
Auftrag 
angefordert 
Instandhaltungs- 
Auftrag 
in Arbeit 
© Siemens AG 2007