5.  SYSTEM PARAMETERS
Parameter
Function
Range
[Default]
Description / Notes
G85139-H1750-U049-B
© Siemens plc 1997
26/09/97
22
P004  
Smoothing (seconds)
0 - 40.0
[0.0]
Used to smooth the acceleration/deceleration of the motor (useful in
applications where it is important to avoid ‘jerking’, e.g. conveyor
systems, textiles, etc.).
Smoothing is only effective if the ramp up/down time exceeds 0.3 s.
Frequency
f
max
(P013)
0 Hz
Time
Total acceleration time
= 15 s
P002 = 10 s
P004
= 5 s
P004
= 5 s
Note:
The smoothing curve for deceleration is based on the ramp
up gradient (P002) and is added to the ramp down time set
by P003. Therefore, the ramp down time is affected by
changes to P002.
P005  
Digital frequency setpoint (Hz)
0 - 400.00
[5.00]
Sets the frequency that the inverter will run at when operated in digital
mode. Only effective if P006 set to ‘0’.
P006
Frequency setpoint source
selection
0 - 2
[0]
Sets the control mode of the inverter.
0 = Digital. The inverter runs at the frequency set in P005.
Alternatively, if P007 is set to zero, the frequency may be 
controlled by setting any two of binary inputs P051 - P053 to
values of 11 and 12.
1 = Analogue. Control via analogue input signal.
2 = Fixed frequency or motor potentiometer. Fixed frequency is
only selected if the value of at least one binary input (P051 -
P053) = 6, 17 or 18.
Notes:
(1) If  P006 = 1 and the inverter is set up for remote
control operation, the analogue inputs remain active.
(2) Motor potentiometer setpoints via digital inputs
are stored when P011 = 1.
P007
Keypad control
0 - 1
[1]
0 = Front panel buttons disabled (except STOP, 
 and 
). Control is
via digital inputs (see parameters P051 - P053)
 and 
 may still
be used to control frequency provided that P124 = 1 and a digital
input has not been selected to perform this function.
1 = Front panel buttons enabled (can be individually disabled
depending on the setting of parameters P121 - P124).
Note: The digital inputs for RUN, REVERSE, JOG and increase/
decrease frequency are disabled.
P009  
Parameter protection setting
0 - 3
[0]
Determines which parameters can be adjusted:
0 = Only parameters from P001 to P009 can be read/set.
1 = Parameters from P001 to P009 can be set and all other
parameters can only be read.
2 = All parameters can be read/set but P009 automatically resets to 0
when power is removed.
3 = All parameters can be read/set.