SITRANS LC 500 – INSTRUCTION MANUAL
Page 53
mmm
mm
Troubl
esho
ot
ing
Error Messages and Error Codes
Error Messages (push-button operation)
Error Codes (HART)
Error 
Message
Description
Cause
Flt
a
 
a.
Alternates with the primary variable (PV).
Fault/failure has been detected
• Device  is  faulty
• Possible short circuit in the probe or the 
device wiring
• Possible fault in the device, or lack of 
sufficient energy at the device 
terminals
ooL
Output out-of-limits 
The product level has risen above the 
Upper Sensor LImit, or fallen below the 
Lower Sensor Limit
Error 
Code
Description
Cause
32
program memory checksum error Device is faulty
16
signal error: the measurement 
circuitry stopped functioning
Possible short circuit in the probe or the device 
wiring
8
DAC drive failure: the current as 
set by the DAC does not match 
the value measured by the ADC
Possible fault in the device, or lack of sufficient 
energy at the device terminals
0
PV value is outside the limits set 
(USL and LSL)
Usually indicates a fault in the connection 
between the transmitter module and the probe 
(the coaxial connector is off)