TC12 Installation, Commissioning & Maintenance Handbook 
666/HE/43100/000  
Page 183 
Issue 9 
 
U
ENG 203 - 210 0 to 255 
 
U
OTUSRx - Integral OTUs shared RAM sections 0-7 
 
These eight codes can be used to display any byte within the shared RAM 
interface between the Integral OTU and the controller. For ease of use, it is 
recommended that the 'ENO' command is used rather than this one. 
 
For example, to access byte number 234 (hex): 
  2XX requires OTUSR2, i.e. ENG 205 
  34 hex is 52 in decimal, therefore the command will be: 
  ENG 205 52 
 
6.4.3  Examples of Lamp Monitor Unit Configuration Using the Handset 
The LMU is configured via the handset and there are several example 
configurations detailed on the following pages. The main items of data to be 
entered and their associated handset commands are listed below: 
 
- Define the type of output to be monitored by each current sensor (KPT) 
 
- Allocate an aspect drive identity to each current sensor (KAD) 
 
- Select normal lamp monitoring (i.e. NOT Red Lamp Monitoring) for each vehicle 
phase (KRE) 
 
Depending on the controller configuration, the following additional data may need 
to be entered: 
 
- If the controller does not have dimming fitted, disable dim/bright checking (KDP) 
 
- If the controller enters a flashing red/amber mode (export only), define the input 
to disable monitoring during the flashing period (KFD) 
 
- To monitor 50-0-50 lamps, select low voltage operation (KLV) 
 
U
Example 1 - Simple 2 phase controller 
 
Description: This is an intersection controller with 2 vehicle phases and lamp 
dimming. 
 
The configuration commands are detailed below. 
 
Enable LMU write access: 
  AMB = 35 
  NEC = 249 
   
Allocate function of each current sensor: 
  KPT 1 = 1 
 
:current sensor 1 monitors a vehicle phase