One disconnect shall be common to the 
drive controller and bypass contactor. 
2. Barriered bypass shall consist of 
compartmentalized, multi-door enclosure 
construction that provides electrical 
isolation of the AC Drive controller from the 
bypass contactor using two OSHA and UL 
approved disconnects. This configuration 
shall remove all power to the drive 
controller compartment when the drive 
disconnect is in the open position.   This 
configuration shall allow provide maximum 
user flexibility if servicing a drive while 
remaining on bypass.
b. A TEST-NORMAL selector switch shall be 
used with bypass to allow testing of the AC 
Drive without running the motor. In the “Test” 
position the isolation contactor shall remain 
open preventing motor operation while 
operating the AC drive.
c. The operator shall have full operational control 
of the bypass starter using a door mounted 
AFC/OFF/BYPASS selector switch.
d. Auto transfer to bypass function shall be 
provided in the event of drive fault or failure. 
This feature shall be enabled or disabled by an 
internally mounted selector switch. An 
adjustable timer shall provide control of the 
delay time between fault and transfer to 
bypass.
2.16 HARMONIC MITIGATION EQUIPMENT 
REQUIREMENTS
Note to Specifier: There are several solutions for 
effective harmonic mitigation. The most common 
approach is the use of a 5% line reactor. When 
line reactors are properly sized for the drive 
controller, the additional source impedance can 
add provide effective levels of harmonic mitigation 
for voltage distortion and attenuation of incoming 
voltage transients. The alternate approaches 
include the use of isolation transformers and 
harmonic filters. The typical installation of 
isolation transformers and filters are separately 
mounted with proper branch circuit protection. 
Filters require coordination with the AC Drive 
power circuit and must not be part of the bypass 
path. An alternate approach is the use of multi-
pulse drives, which are typically specified above 
100 hp.
a. The AC Drive shall be provided with a 5% 
rated line reactor mounted inside the 
enclosure.
b. The AC Drive shall provide provisions and 
terminations inside the drive enclosure for 
branch circuit protection of a separately 
mounted isolation transformer or harmonic 
filter. The AC Drive disconnect shall serve as 
disconnect for the harmonic filters. Branch 
circuit protection shall be in accordance with 
the NEC using fused protection. Harmonic 
filters shall be isolated from bypass path 
operation if supplied. 
2.17 HARMONIC ANALYSIS
Note to Specifier: Guidelines for voltage and 
current distortion are addressed in IEEE Standard 
519-1992 titled “IEEE Recommended Practices 
and Requirements for Harmonic Control in 
Electrical Power Systems”, which suggests 
distortion limits dependent upon the electric 
power distribution system for industrial and 
commercial consumers. Collectively, all facility 
loads and the building electrical distribution 
network determines the harmonic levels at the 
user & electric utility interface. The Electrical 
Power Research Institute (EPRI) recognizes the 
‘Point of Common Coupling’ or PCC as the 
interface between user and electric utility (energy 
meter) in the electrical distribution network. The 
AC Drives manufacturer can provide calculations 
through computer modeling, specific to the 
installation, showing total harmonic voltage 
distortion. Contractor to provide one line diagram 
drawings to supplier including transformer 
impedance. The AC Drive manufacturer needs 
this information.
a. A harmonic distortion analysis shall be 
performed and priced as a separate line item 
by the AC Drive manufacturer based upon 
documentation supplied by the contractor. The 
documentation shall consist of one-line 
diagrams, distribution transformer information 
(kVA, %Z, and X/R ratio) and emergency 
standby generator performance 
specifications. The harmonic distortion 
analysis report shall be part of the approval 
drawing process, submitted to the engineer for 
approval.
b. If the calculations determine that harmonic 
distortion values are higher than the voltage 
and current values specified, the drive 
manufacturer shall provide [line reactors, 
isolation transformers, harmonic suppressors]
 
to meet the intent of IEEE 519-1992 
guidelines.