Assignment of Logic Outputs (R2 or LOx)
©
 2000–2003 Schneider Electric All Rights Reserved
62
09/2003
Current Level Attained 
The logic output is high (state 1, 24 Vdc nominal) if the motor current is greater than or equal to the 
configured current level. The current level is factory set at 136% and has an adjustable range of 25 to 
136% of the drive controller’s constant torque rating.
Motor Thermal Level Attained
The logic output is high (state 1, 24 Vdc nominal) if the motor thermal state is greater than or equal to 
the configured motor thermal level. The motor thermal level is factory set at 100% and has an adjustable 
range of 0 to 118%. 
Drive Thermal Level Attained
The logic output is high (state 1, 24 Vdc nominal) if the drive thermal state is greater than or equal to 
the configured drive thermal level. The drive thermal level is factory set at 105% and has an adjustable 
range of 0–118%
Loss of Follower (4–20 mA Signal)
The logic output is high (state 1, 24 Vdc nominal) if the signal on the 4–20 mA speed reference input is 
less than 2 mA.
Brake Logic Command
This is a set of parameters that allows control of a mechanical brake by the drive controller.
The brake release is determined by brake release frequency, brake release current threshold, and brake 
release time delay. The brake engage is determined by the brake engage frequency and brake engage 
time.
Parameters accessible in the Adjust menu:
• Brake release frequency (brL).
• Brake release current (Ibr).
• Brake release time (brt).
• Brake engage frequency (bEn).
• Brake engage time (bEt).
NOTE: Unlike the 
previous 
assignments, which 
may be assigned to 
either relay R2 or one 
of the logic outputs 
(LOx), Brake Logic 
Command can only 
be assigned to relay 
R2.
Reference
Brake state
 R2 relay
Motor current
Motor frequency
bEn
Ibr
brL
brt
T
bEt
Motor Speed
Increasing or decreasing
1
0
1
0
1
0
T = non-adjustable delay