Mounting in a General-Purpose Metal Enclosure
To ensure sufficient air circulation when mounting an ATV58 TRX drive in a general-purpose enclosure, 
observe the following:
• Provide ventilation inlets and outlets in the enclosure (see the figure below).
• If the enclosure does not provide sufficient free air flow, install an enclosure ventilation fan with 
IP54/NEMA 12 filters to exhaust heat outside of the enclosure (see the figure above). The enclosure 
fan should have a greater fan flow rate than the drive controller fan flow rate listed in the table below.
• If there is a possibility of condensation, keep the control supply switched on during periods when the 
motor is not running, or install thermostatically controlled strip heaters.
Mounting in a Type 12 or IP54 Metal Enclosure
Certain conditions may require Type 12 or IP54 protection, such as dust, corrosive gas, high humidity 
with the risk of condensation and dripping water. When mounting in a Type 12 or IP54 enclosure, follow 
the installation recommendations given on page 97.
If the enclosure is non-ventilated, use a stirring fan to circulate the air inside the enclosure to prevent 
hot spots from forming. With a stirring fan, the maximum temperature inside the enclosure can then be 
up to 60 °C (140 °F), although the current must be derated by 2.2% per °C above 50 °C. If condensation 
might form within the enclosure, keep the power supply switched on during periods when the motor is 
not running, or install thermostatically controlled strip heaters.
ATV58 TRX Model
Fan Flow Rate
ATV58HU09M2, ATV58U18M2
Non-Ventilated
ATV58HU29M2, ATV58U18N4, ATV58U29N4, ATV58U41N4, ATV58U54N4
36 m
3
/hour
21 CFM
ATV58HU41M2
47 m
3
/hour
27.5 CFM
ATV58HU54M2, ATV58U72M2, ATV58U54N4, ATV58U72N4, ATV58U90N4
72 m
3
/hour
42 CFM
ATV58HU90M2, ATV58D12M2, ATV58D12N4, ATV58D16N4, ATV58D23N4
72 m
3
/hour
42 CFM
ATV58HD16M2, ATV58D23M2, ATV58D28N4, ATV58D33N4, ATV58D46N4
161 m
3
/hour
94 CFM
ATV58HD28M2, ATV58D33M2, ATV58D46M2, ATV58D54N4, ATV58D64N4, ATV58D79N4
343 m
3
/hour
200 CFM
ATV58HC10N4X
600 m
3
/hour
350 CFM
ATV58HC13N4X, C15N4X, C19N4X
900 m
3
/hour
525 CFM
ATV58HC23N4X, C25N4X, C28N4X, C31N4X, C33N4X
900 m
3
/hour
525 CFM
with fan and filter
mounted on enclosure
free air flow