DV425TR DIRECT VENT ROOM HEATER
02/01                                                                                     Page 40                                                                               250-5533
Step 1.
 
Before cutting any holes, assemble the desired sections of direct vent pipe to determine the center 
of the masonry penetration.
Step 2.
 
Once the center point of the penetration has been determined, cut a 6” (152mm) diameter hole in the 
masonry. If the hole is too large, the retro connector might not mount properly; if the hole is too small, the 
appliance might starve for intake air. If there is a frame wall in front of the masonry wall, cut and frame a 
10” (254mm) square opening in the wall (centered around the 6” [152mm] masonry opening). If there is sheet 
rock only (no studs) in front of the masonry the 10” (254mm) opening is still needed, but does not need to be 
framed. This allows the retro connector to mount directly on the masonry and provide the correct clearances 
to combustibles (see Figure 22).
VERTICAL INSTALLATION, cont.
INSTALLATION INTO AN EXISTING MASONRY CHIMNEY
 (USA ONLY)
Fig. 22
NOTE:  FOR HEARTH 
APPLICATIONS REFER TO 
PAGE 24 FOR THE USE 
OF THE 923GCL CO-AXIAL 
TO CO-LINEAR APPLIANCE 
CONNECTOR.
10" x 10" FRAMED 
OPENING IN WALL
STUDWALL
MASONRY 
CHIMNEY
RETRO 
CONNECTOR
(4) MASONRY BOLTS 
(NOT INCLUDED)
WALL THIMBLE 
COVER