If the trouble does not appear to be in the burner or 
ignition hardware, check the oil primary control and the 
ignitor by using the following equipment: 
à  screwdriver. 
à  voltmeter (0 - 150 
VAC
à  insulated jumper wires with both ends stripped. 
 
Electrical Shock Hazard
Troubleshooting is done with the system powered. Be 
careful to observe all necessary precautions to prevent 
electrical shock or equipment damage. 
Preliminary Checks
1.  Make sure that limit switches are closed and that 
contacts are clean. 
2.  Check for line voltage power on the oil primary 
control black and white lead wires. 
3. Refer to Table C-4 or C-5 for further 
troubleshooting information. 
 
TABLE C-3:  R7184 TROUBLESHOOTING
 
Condition: Burner motor does not start when there is a call for heat. 
Procedure Status 
Corrective 
Action 
1.  Check that limit switches 
are closed and contacts 
are clean. This includes 
the burner motor reset 
button. 
N/A N/A 
2.  Check for line voltage 
power at the oil primary 
control. Voltage should 
be 120 Vac between the 
black and white lead 
wires on the oil primary 
control. 
N/A N/A 
Indicator light is on. 
Cad cell is defective, sees external light, or 
connections have shorted. Go to step 4. 
3.  Check indicator light with 
burner off, no call for heat 
(no flame). 
Indicator light is off. 
Go to step 5. 
Indicator light turns off. 
Eliminate external light source or permanently 
shield cad cell. 
4.  Shield cad cell from 
external light. 
Indicator light stays on. 
·  Replace cad cell with new cad cell and 
recheck. 
·  If indicator light does not turn off, remove 
yellow leadwires from R7184 and recheck. 
·  If indicator light is still on, replace the R7184 
control. 
·  If the indicator light turns off, replace cad cell 
bracket assembly. 
· 
continued on following page