Commander Installation Guide 
Page 
16 
of 
81 
       
 
Issue 9 
Trilogy Communications Limited 
 
2.5  MAINS CONNECTION AND FUSING 
 
2.5.1  500-15-30 SERIES POWER SUPPLY 
The PSU chassis occupies an additional 2U of rack space below the matrix and is internally 
wired. The complete assembly therefore occupies 8U for a 96 port system, 14U for a 192 
port system etc. The PSU is half rack width allowing two PSU modules to be fitted, thus 
providing backup operation. 
Each power supply is fitted with a D9 socket, which provides a relay contact indicating the 
PSU status. The table below gives details. Connection should only be made to the pins 
indicated: any other connections may cause failure of the power supply unit. There is also an 
auxiliary power connector: details below. 
 
D9 Fixed Plug Pin  Function 
Relay normally closed 
Relay normally open 
3 Relay 
common 
 
 
XLR4 Fixed Socket Pin 
Function 
1 0V 
2 +15V 
3 No 
connection 
4 -15V 
 
The power supplies are switched-mode units and will cope automatically with an input 
voltage of between 98 and 260 volts AC. This should be wired according to the instructions 
provided with your mating mains socket using suitable cable. See below for earthing details. 
The mains plug has an integral fuse tray fitted with a 20mm glass cartridge slow blow/anti-
surge fuse. The fuse rating is marked adjacent to each fuse tray. 
 
2.5.2  EARTHING REQUIREMENTS 
The Trilogy 500-15-30 units are provided with a single 4mm-earthing stud on the rear panel. 
Incoming mains earth from the IEC connector is internally bonded to both the chassis and 
technical 0V to meet safety requirements and performance specifications. The stud allows 
the addition of an earth strap in rack installations. 
Note: The Aux power connector is protected by an internal self-resetting thermal fuse. Left 
and right (main and standby) supplies may be connected in parallel.