Error code
Failure code
Problem
Possible causes
Remedies
QJ
002E
External thermal trip
• An external thermal trip is input.
• Check the external thermal input.
G
0011
Emergency stop
• During automatic operation or remote
operation, a stop command is entered
from the operation panel or a remote
input device.
• Reset the inverter.
GGR
0012
EEPROM fault 1
• A data writing error occurs.
• Turn off the inverter, then turn it again. If it
does not recover from the error, make a
service call.
GGR
0013
EEPROM fault 2
• Power supply is cut off during V[R
operation and data writing is aborted.
• Turn the power off temporarily and turn it
back on, and then try V[R operation
again.
GGR
0014
EEPROM fault 3
• A data reading error occurred.
• Turn off the inverter, then turn it again. If it
does not recover from the error, make a
service call.
GTT
0015
Main unit RAM fault
• The control RAM is defective.
• Make a service call.
GTT
0016
Main unit ROM fault
• The control ROM is defective.
• Make a service call.
GTT
0017
CPU fault 1
• The control CPU is defective.
• Make a service call.
GTT
0018
Remote control error
• An error arises during remote operation.
• Check the remote control device, cables,
etc.
GTT
001A
Current detector fault
• The current detector is defective.
• Make a service call.
GTT
001B
Optional circuit board
format error
• An optional circuit board in a different
format is installed.
• Check again to be sure that the circuit
board is connected correctly, and then
reset the power supply.
• Replace the circuit board with a correctly
formatted one.
*
WE
001D
Low-current
operation
Trip
• The output current decreased to a low-
current detection level during operation.
• Enable H (low-current detection).
• Check the suitable detection level for the
system (H, H).
• Make a service call if the setting is
correct.
*
WR
001E
Undervoltage trip
(main circuit)
• The input voltage (in the main circuit) is
too low.
• Check the input voltage.
• Enable H (undervoltage trip
selection).
• To cope with a momentary stop due to
undervoltage, enable H (ride-
through control) and H (auto-
restart).
GH
0022
Ground fault trip
• A ground fault occurs in the output cable
or the motor.
• Check the cable and the motor for ground
faults.
GVP
0054
Auto-tuning error
• Check the motor parameter H to H.
• The motor with the capacity of 2 classes or less than the inverter is used.
• The output cable is too thin.
• The motor is rotating.
• The inverter is used for loads other than those of three-phase induction motors.
GV[R
0029
Inverter
type error
• Circuit board is changed.
(Or main circuit/drive circuit board)
• Make a service call.
*
G
0032
Brea in analog signal
cable
• The signal input via VIA is below the
analog sinal detectio level set with
H
.
• Check the cables for breaks. And check
the setting of input signal or setting value
of H.
G
0033
CPU
communications
error
• A communications error occurs between
control CPUs.
• Make a service call.
G
0034
Excessive torque
boosted
• The torque boost parameter H is
set too high.
• The motor has too small impedance.
• Decrease the setting of the torque boost
parameter H.
G
0035
CPU fault 2
• The control CPU is defective.
• Make a service call.
UQWV
002F
Step-out
(For PM motor only)
• The motor shaft is locked.
• One output phase is open.
• An impact load is applied.
• Unlock the motor shaft.
• Check the interconnect cables between
the inverter and the motor.
* You can select a trip ON/OFF by parameters.