National Instruments Welding System 321645c-01 Manual De Usuario

Descargar
Página de 554
Chapter 2
Function Reference — DIG_Block_Clear
NI-DAQ FRM for PC Compatibles
2-148
©
 National Instruments Corporation
DIG_Block_Clear
Format
status = DIG_Block_Clear (deviceNumber, group)
Purpose
Halts any ongoing asynchronous transfer, allowing another transfer to be initiated.
Parameters
Input
Parameter Discussion
group is the group involved in the asynchronous transfer.
Range:
1 or 2 for most devices.
1 through 8 for the DIO-96.
Using This Function
(AT-DIO-32F only) If you aligned the buffer that you used in the previous call to 
DIG_Block_Out
 or 
DIG_Block_In
 by a call to 
Align_DMA_Buffer
DIG_Block_Clear
 
unaligns that buffer before returning. Unaligning a buffer means that the data is shifted so that 
the first data point is located at buffer[0].
After NI-DAQ has started a block transfer, you must call 
DIG_Block_Clear
 before NI-DAQ 
can initiate another block transfer. Notice that 
DIG_Block_Check
 makes this call for you 
when it sees that NI-DAQ has completed a transfer. 
DIG_Block_Clear
 does not change any 
current group assignments, alter the current handshaking settings, or affect the state of the 
pattern generation mode.
Name
Type
Description
deviceNumber
i16
assigned by configuration utility
group
i16
group