Chapter 2
Function Reference — SCAN_Start
©
 National Instruments Corporation
2-313
NI-DAQ FRM for PC Compatibles
you cannot control the scan interval externally. In this case, NI-DAQ scans the 
channels repeatedly as fast as you apply the external conversion pulses.
Note
Simultaneous sampling devices ignore parameters for sampTimebase and 
sampInterval. These devices sample all channels simultaneously. The acquisition 
rate is controlled by 
scanTimebase and scanInterval; therefore, a scanInterval 
value of 0 is not allowed.
Using This Function
SCAN_Start
 initializes the Mux-Gain Memory table to point to the start of the scan sequence 
as specified by 
SCAN_Setup
. If you did not specify external sample-interval timing by the 
DAQ_Config
 call, NI-DAQ sets the sample-interval counter to the specified sampInterval 
and sampTimebase, sets the scan-interval counter to the specified scanInterval and 
scanTimebase, and sets up the sample counter to count the number of samples acquired and 
to stop the data acquisition process when the number of samples acquired equals count. If you 
have specified external sample-interval timing, the data acquisition circuitry relies on pulses 
received on the EXTCONV* input to initiate individual A/D conversions. In this case, 
NI-DAQ scans the channels repeatedly as fast as you apply the external conversion pulses.
SCAN_Start
 initializes a background data acquisition process to handle storing of A/D 
conversion samples into the buffer as NI-DAQ acquires them. When you use posttrigger mode 
(with pretrigger mode disabled), the process stores up to count A/D conversion samples into 
the buffer and ignores any subsequent conversions. NI-DAQ stores the acquired samples into 
the buffer with the channel scan sequence data interleaved; that is, the first sample is the 
conversion from the first channel, the second sample is the conversion from the second 
channel, and so on.
You cannot make the second call to 
SCAN_Start
 without terminating this background data 
acquisition process. If a call to 
DAQ_Check
 returns daqStopped = 1, the samples are available 
and NI-DAQ terminates the process. In addition, a call to 
DAQ_Clear
 terminates the 
background data acquisition process. Notice that if a call to 
DAQ_Check
 returns an error code 
of overFlowError or overRunError, or daqStopped = 1, the process is automatically 
terminated and there is no need to call 
DAQ_Clear
.
If you enable pretrigger mode, 
SCAN_Start
 initiates a cyclical acquisition that continually 
fills the buffer with data, wrapping around to the start of the buffer once NI-DAQ has written 
to the entire buffer. When you apply the signal at the stop trigger input, 
SCAN_Start
 
acquires an additional number of samples specified by the ptsAfterStoptrig parameter in 
DAQ_StopTrigger_Config
 and then terminates. Be aware that a scan sequence always 
completes. Therefore, NI-DAQ always obtains the most recent data point from the final 
channel in the scan sequence. When you enable pretrigger mode, the length of the buffer, 
which is greater than or equal to count, should be an integral multiple of numChans. If you 
observed this rule, a sample from the first channel in the scan sequence always resides at 
index = 0 in the buffer.