OPERATION  OF THE  SYSTEM
WTC 600 LP / MP
Service Handbook 08.2004
5. For 75% yield:
Total x 128 = _____ ml RM 852 per 10 litre metering solution
OR
Total x 34
8
 = _____ ml calcium hypochlorite (1ml corresponds to 1.05g) per 10 litres metering solution
These values are entered in the customer's operating instructions.
Calculation example:
- Yield 75%
- Iron (Fe) 1.0 mg/l
- Manganese (Mn) 1.0 mg/l
- Ammonium (NH
4
) 0.2 mg/l
Iron content:
1,0 x
0,4 =
0,4
Manganese content:
1,0 x
0,6 =
0,6
Ammonium content:
0,2 x
8,0 =
1,6
Basic requirement:
1,2
Total:
   3,8
For 75% yield:
Total x 128 = 486 ml RM 852 per 10 litre metering solution