Horizontal Termination
„
Any horizontal termination must fall within the
shaded portion of the vent window graph illustrated
in figs. 9 or 11.  For Snorkel Terminations, see below.
„
Any horizontal termination except a snorkel termination,
must include:
1)
Minimum rise of 2 ft.
2)
Minimum horizontal run of 12 in. when vertical
run is less than 8 ft.
2)
Maximum rise of 35 ft.
3)
Maximum horizontal run of 27 ft.
4)
No more than four 45° or two 90° Elbows
„
Follow all termination clearance guidelines as speci-
fied in fig. 19.
„
The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
2 1/2" or less. It must also maintain 12" clearance
from projections exceeding 2 1/2".  See fig. 20.
„
Wall Cut-out Opening: A minimum 10" X 10" (250 mm x
250 mm) square hole is required for proper pipe clear-
ances through a combustible wall. Use a listed wall
thimble for the wall penetration.
DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.
„
Any horizontal run of vent must have a 1/4" rise for
every foot of run toward the termination cap. NEVER
ALLOW THE VENTING TO RUN DOWNWARD FROM
STOVE TO TERMINATION; DOWNWARD VENT RUNS
TRAP HEAT AND CAUSE HIGH TEMPERATURES TO
DEVELOP WITHIN THE VENT THAT COULD START A
FIRE.
„
Install a Vinyl Siding Standoff between the vent
termination and an exterior wall covered by vinyl
siding material to prevent potential heat damage to
the siding.
„
Do not recess the termination cap into a wall or
siding.
Figure 16.
• Minimum vent for horizontal termination.
• 14” Maximum horizontal run directly off rear of stove
with 14” Snorkel termination.
Figure 17.  Maximum Horizontal and Vertical Run with 36”
Snorkel Termination.
Max.
6 ft.
183 cm
36 in.
Snorkel
(915 mm)
Figure 18.  Corner Installation with 14” Snorkel Termination.
Snorkel  Terminations
„
THE AIR INLET RESTRICTOR MUST BE SET FULLY OPEN
FOR ANY SNORKEL TERMINATION. 
See Fig. 6, pg. 9.
„
With a 14” Snorkel:
The horizontal run made directly off the rear of the
stove into a 14” snorkel cap should include no more
than a single 12” straight section as shown in fig. 17.
One 45° Elbow may be used for a corner installation as
shown in fig. 18.
„
With a 36” Snorkel:
The maximum horizontal run may be no more than
6 ft. (182 cm.)
12 in.
Straight Pipe
Max.
14”
355 mm
Wall Thimble
and Trim Collar
45° Elbow
See Note F
Fig. 20
CL
14”
355 mm
Max.
12 in.
(305 mm)
12”
Vent
Pipe or
less
57”
(1448 mm)
24 in.
Snorkel
(305 mm)
25 1/2 in.
Snorkel
(648 mm)