Fuel                     
Type
Inlet Pressure
Manifold Pressure
Desired Minimum Maximum
On Hi 
Fire
On Lo 
Fire
Natural
Gas
7" WC
5" WC
10.5" WC
3.5" WC 1.7" WC
LP Gas
11" WC 11" WC
13" WC
11" WC
5.4” WC
Gas Line Installation 
The Ravelle™ 42 gas fireplace must be connected to the gas line in ac-
cordance with local codes and/or the National Fuel Gas Code, ANSI Z223.1 
(In Canada, the current CAN/CSA  B149.1 installation code). The gas line 
should enter the fireplace on the left side (see diagrams on Pages 8 and 
9). If the gas line enters the unit from the right side, the line will need to 
be disconnected to remove the fan. The fireplace comes with a flex line 
attached to the supply side of the gas valve. The fitting on the end of the 
flex line can receive a 1/2” female iron pipe coupling, a 3/8” male iron 
pipe, or a shut-off valve. There is sufficient room to locate the shut-off 
valve under the firebox at the end of this flex line, however, local codes 
may require the shut-off to be located on the exterior of the fireplace. After 
connecting the gas line, all joints in the line and connections at the valve 
should be checked for leaks before final positioning of the unit. Conduct a 
gas leakage test of the appliance piping and control system downstream 
of the shutoff valve in the supply line to the appliance.
Gas Pressure Requirements
A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLI-
ANCES IS IMPROPER GAS PRESSURE!
The most important item to check during the initial installation 
and the first thing to check when operating problems occur is 
gas pressure! 
This fireplace will not function properly unless the required 
gas pressure is supplied. See the table on this page for gas 
pressure requirements.
Two pressure taps are provided on the fireplace’s valve to check gas 
pressures. To access the taps remove the two socket head screws to 
remove the valve control panel/heat shield. The taps are located below 
the on/off/pilot knob (see Figure 32). The left tap is the inlet (supply) 
pressure side. To check inlet pressure (with the fireplace burning) insert 
a small flat bladed screwdriver into the tap and turn a half turn counter-
clockwise. Cover the tap with the line from a manometer and read the 
pressure. Close the tap gently but securely after completing the check. 
The manifold (outlet) tap is to the right of the inlet tap. To check manifold 
pressure (with the fireplace burning at the high burn setting) insert a 
small flat bladed screwdriver into the tap and turn a half turn counter-
clockwise. Cover the tap with the line from the manometer and check 
the pressure. Again close the tap gently but securely after completing 
the check. Check the taps for gas leaks with a gas leak test solution 
(retighten if necessary).
If the pressure is not sufficient, make sure the gas supply line is large 
enough, the supply regulator is properly adjusted and the total gas load 
for the residence does not exceed the amount supplied.
Propane tanks are at pressures that will cause damage to valve com-
ponents.  Verify that the tanks have step down regulators to reduce the 
pressure to safe levels.
LP and Natural Gas Supplies
Your  Ravelle  gas  fireplace  is  equipped  from  the  factory  for  use  with 
natural gas only as specified on the Safety / Listing label attached to the 
appliance. This appliance can only be operated using propane gas (LP) 
if a certified fuel conversion kit provided by Lennox Hearth Products is 
installed by a qualified service technician.  
Also check the orifice size on the label on the igniter bracket. It must be 
the correct size for the fuel and altitude.
Do not run propane tank dry.  Running the tank dry may cause a 
hazardous condition due to pressure drop in empty tank. 
Solid fuel is NOT to be used with this unit.
Note:  The appliance and its individual shut-off valve must be disconnected 
from the gas supply piping system during any pressure testing of that 
system at test pressures in excess of 1/2 psig. The appliance must be 
isolated  from  the  gas  supply  piping  system  by  closing  its  individual 
manual shut-off valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psig. Check with your 
gas supplier or plumber.
Inlet (Supply) 
Pressure Tap
Figure 32
The Manifold
(Outlet) Tap
TP/TH
TH
TP
SIT Millivolt Gas Valve
These appliances must be isolated from the gas supply piping system 
(by closing their individual manual shut-off valve) during any pressure 
testing of the gas supply piping system at test pressures equal to or 
less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be discon-
nected from the gas supply piping system during any pressure testing 
of that system at pressures greater than 1/2 psig (3.5 kPa).