COMMAND>INP O
INPUT OPERATIONS
===== ==========
1 = Input Dampening:        Enabled
2 = Input Deadband:         1
3 = Rate of change period:  00:00:10 (hh:mm:ss)
0 = Previous Menu
Choose a Number>2
Enter New Deadband in ADC counts> 1
Rate-of-Change Period
The rate of change period is the period of time that a Messenger 570 waits in before taking the samples that
are to be used in the rate of change alarm checks.  Note:  This time period only applies to the rate of change
set point checks.  All other set points are checked and acted upon once every 100 ms. 
„
  Input Setup Parameters
Type INP S at the command prompt to control the configuration parameters for each input. You will get a list
of all configurable inputs. Select the input you wish to configure and you will get a sub-menu containing
parameters for that input.
COMMAND>INP S
SET/CHECK INPUT SETTINGS
========= ===== ========
1 = Input #1  <Label>
2 = Input #2  <Label>
3 = Input #3  <Label>
4 = Input #4  <Label>
5 = Input #5  <Label>
6 = Input #6  <Label>
7 = Input #7  <Label>
8 = Input #8  <Label>
0 = Previous Menu
Choose a Number>1
Input #1
PRESENT SETTINGS
======= ========
01 = Label                  <Label>
02 = Sensor Type            Temperature (°F)
03 = High Alarm Set Point   260
04 = Low Alarm Set Point    -94
05 = Response Time          0 Sec.
06 = Output On Set Point    260
07 = Output Off Set Point   -94
08 = Calibration Offset     0
09 = Data Logging           Enabled
00 = Previous Menu
Choose a Number>