HP Performance Optimized Data Center (POD) 40c Manual De Usuario

Descargar
Página de 84
 
Environmental control system  53 
To set the HP POD 40c G2 serial number in the ECS: 
1. 
Select POD S/N. 
A keypad appears. 
2. 
Enter the HP POD 40c G2 serial number. For more information, see "Parts and part number 
identification (on page 
)." 
3. 
Select Save to store the new parameters in the system configuration file. 
 
Controller Settings screen 
You can only access this screen after you have entered a service-level password. 
The Controller Settings screen displays the control setpoints for each major system component. 
 
You can set the following configuration options: 
 
Control routine interval 
 
Chilled water supply and return differential temperature setpoint (default = 12ºC (10°F)) 
 
Temperature and pressure setpoints 
 
Temperature and pressure time constants 
 
Differential temperature and pressure P and I gain 
 
Temperature P, I, and D gain