Environmental control system 53
To set the HP POD 40c G2 serial number in the ECS:
1.
Select POD S/N.
A keypad appears.
A keypad appears.
2.
Enter the HP POD 40c G2 serial number. For more information, see "Parts and part number
identification (on page
identification (on page
)."
3.
Select Save to store the new parameters in the system configuration file.
Controller Settings screen
You can only access this screen after you have entered a service-level password.
The Controller Settings screen displays the control setpoints for each major system component.
The Controller Settings screen displays the control setpoints for each major system component.
You can set the following configuration options:
•
Control routine interval
•
Chilled water supply and return differential temperature setpoint (default = 12ºC (10°F))
•
Temperature and pressure setpoints
•
Temperature and pressure time constants
•
Differential temperature and pressure P and I gain
•
Temperature P, I, and D gain