Cooling system  59 
Cooling system 
HP POD 20c cooling system theory of operation 
  
 
CAUTION: 
 Using contaminated supply water can cause decreased cooling capacity or 
disruption in service. The supply water must meet the guidelines stated in the HP Performance 
Optimized Datacenter 20c Site Preparation and Requirements Guide
. Damage caused by 
contaminated supply water is not covered by the warranty. 
  
The HP POD 20c has six heat exchangers configured in three zones that maintain temperature and cool the 
equipment installed in the HP POD 20c. The HP POD 20c receives chilled water from your facility, cycles the 
water through the heat exchangers to cool the air, and then the fans circulate the cool air throughout the HP 
POD 20c. 
A predetermined differential pressure setpoint between the hot aisle and the cold aisle is factory set. Do not 
alter the setpoint without consulting HP. The speed of the fan units is regulated to maintain the differential 
pressure between the hot aisle and the cold aisle. For more information, see "Fans (on page 
)." 
The HP POD 20c chilled water flow rate is not regulated by the ECS system. Site control over chilled water 
flow rate is necessary to allow 454 lpm (120 gpm
*
). 
For more information on the cooling system, see the HP POD 20c Maintenance and Service Guide
 
*
Measurement is in US gallons per minute. 
 
Water supply temperature 
The temperature of the water supplied to the HP POD 20c must be 13ºC to 24ºC (55ºF to 75ºF). Freezing 
water can cause a blockage and damage to the POD.