Cooling system  63 
Depending on the IT equipment installed in your HP POD 20c, you can choose to change both default 
parameters to improve the overall efficiency of your system. To discuss the effects of changing these 
parameters for your specific HP POD 20c, contact HP ("
" on page 
). 
 
 
Item 
Component 
Quantity 
Description 
Fan tray assemblies 
3 banks of 6 (18 
total) fans per zone 
Circulates cool air from the heat exchangers 
throughout the HP POD 20c 
Fan control and power 
supply assembly 
Provides fan speed control, status, and DC power 
for the fans 
 
 
Condensation management 
  
 
CAUTION: 
 To maintain accurate environmental conditions inside the HP POD 20c, do not leave 
the HP POD 20c doors open during operation. 
  
The heat exchanger drip trays collect condensation that forms on the heat exchangers. This collected 
condensation drains out of the HP POD 20c through the heat exchanger condensate drains. HP recommends 
connecting the condensate drains on the HP POD 20c to a facility drain to prevent collection of water near 
the HP POD 20c. 
The HP POD 20c has two 3.18 cm (1.25 in) condensate drain outlets located at both ends of the hot aisle of 
the HP POD 20c. The drain outlets are directly connected to the heat exchanger drip trays. The HP POD 20c 
main supply and return line is connected to the condensate drain line. 
To avoid excessive buildup of condensation and to conserve energy, raise the cooling water temperature to 
above the dew point to manage condensation while maintaining the necessary cooling capacity. 
 
Drains 
  
 
WARNING:
  Water that drains around the HP POD 20c can cause a potential slip hazard. Use 
caution where slip hazards are present.