Removal and replacement procedures  15 
Removal and replacement procedures 
Safety considerations 
The HP POD 40c NA is listed to the UL 69050 standard as an Information Technology Product and Classified 
according to the NEC, NFPA-70, 2008. 
The HP POD 40c NA is not suitable for long term personnel occupancy. 
The safety information is specific to the people operating and maintaining the components of the HP POD 
40c NA. 
   
 
IMPORTANT:
  All plumbing to and from the HP POD 40c NA must be completed by a licensed 
plumber. 
   
   
 
IMPORTANT:
  All wiring in and around the HP POD 40c NA must be completed by a licensed 
electrician. 
   
 
Operator safety 
The HP POD 40c NA is not habitable or suitable for human occupancy. The HP POD 40c NA is Listed as a 
Product that provides service access areas for periodic maintenance and service. These areas must be 
controlled and available for use only by owner-authorized personnel and qualified personnel who are 
trained in the maintenance and service of the HP POD 40c NA components. 
   
 
WARNING:
  To avoid the risk of personal injury or loss of life, all personnel must comply with PPE 
requirements when opening or working inside areas of the HP POD 40c NA that are marked as 
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ). 
   
   
 
WARNING:
  To avoid the risk of personal injury, hearing protection must be worn at all times 
when working inside the HP POD 40c NA. 
   
   
 
WARNING:
  To avoid the risk of personal injury or damage to the equipment, do not insert 
anything inside the electrical busways, except for the approved HP busway drop boxes.   
   
Before completing the installation of the HP POD 40c NA, the customer, or a designated agent, is 
responsible for completing any Environmental Health and Safety evaluation of the HP POD 40c NA or any 
attached structural component purchased through HP. The customer, or their designated agent, must also 
complete an arc flash assessment and breaker coordination study of the HP POD 40c NA and the associated 
electrical supply system for operation and maintenance. The individual or organization that completes the 
arc flash assessment must also create and provide all required labeling for all electrical panels on the HP 
POD 40c NA.