Honeywell Network Hardware NETAXS-123 Manual De Usuario

Descargar
Página de 76
58
www.honeywell.com
Installing the NetAXS-123 Panels
System Configuration
4.10  NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail
Figure 22:    NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail
X
DO NOT CONNECT or 
GROUND SHIELD
Ground only one 
side of cable shield
Shield
Ground Shield
485 -
485 Common
485 +
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON
DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
S7: OFF
S8-S9 OFF: 485 Termination OFF
485 -
485 Com
485 +
DC Out
A
B
COM
+24VDC in
NetAXS-123
C-TB9
485 -
485 Com
485 +
DC Out
A
B
COM
+24VDC in
NetAXS-123
C-TB9
485 -
485 Com
485 +
DC Out
A
B
COM
+24VDC in
NetAXS-123
C-TB9