Installing the NetAXS-123 Panels
Troubleshooting
NetAXS-123 Access Control Unit  Installation GuideDocument 800-05779, Revision A
65
8.0  Troubleshooting
Note:  
The NetAXS-123 EOL network is AC-coupled. There is no resistance 
difference between the RS-485 positive and negative terminals if the EOL network is 
on or off (SW1, switches 8 and 9).
Table 11  Troubleshooting Problems and Solutions
Problem
Solution
The panel 
powers up, but it 
does not respond 
to any 
communication, 
cards reads, or 
input activation.
Ensure that the Address DIP switches are set to a value other than zero. 
Turn off the power (including battery), change the settings, and re-apply 
the power.
No 
communications 
exist with the 
Ethernet port.
Only a panel set to be a Gateway (DIP switch 6 = ON) will have 
communications on the Ethernet port. If you need to use that port to 
access the panel, turn off the power (including the battery), change the 
switch setting, and reapply the power. Note that if the panel is normally 
not a Gateway on a Multidrop communication bus, then the Host 
RS-485 connection (C-TB9) should also be disconnected while DIP 
switch 6 is ON. After completion of the Ethernet session, turn off the 
power (including the battery), change the switch setting, re-connect the 
Host RS-485 terminal block, and re-apply the power.
The panel 
address is 
unknown.
Option 1:  Set the NetAXS-123 panel’s DIP switch 7 to ON. This will 
default the IP address to 192.168.1.150.
Option 2: Connect to the panel through the USB port using the provided 
USB A to MicroUSB B cable and the USB driver on the product CD.  
The default USB Ethernet IP address is:  192.168.2.150.
The N1000 and 
NS2 panels on 
the Multidrop 
bus do not 
report.
N1000 and NS2 panels are not supported downstream from a 
NetAXS-123 panel.  To enable the NetAXS-123 to communicate with 
the N1000 and NS2 panels, the loop must  be configured with an
N-485 PCI-3 as the Gateway. However, in this configuration, web 
functionality is lost.  It is recommended that the user swap-out N1000 
and NS2 panels with NetAXS-123 panels.