T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
15
62-0255—09
Setup Procedure
The Setup process uses a hierarchical menu structure 
that is easy to use. You press the t and u arrow buttons to 
move forward and backward through the menus.
NOTE: The menus can display only those relays that 
are defined in Setup (see “1.3.2. NBR OF 
RELAYS” on page 22). For example, if you 
configure only two relays, then only two 
relays display on the appropriate menus.
To change the controller’s sensors and output setup 
parameters, perform the following procedures in the order 
listed:
1. Enter Setup mode — see “1.1. Entering Setup 
2. Setup Sensors — see “1.2. Setting up the Sensors”
4. Exit Setup Mode — see “1.4. Exiting Setup” on 
1.1. Entering Setup Mode
To enter Setup mode, press and hold the MENU button for 
five seconds to display the Setup menu. See Fig. 24 on 
Fig. 25. Setup - Sensors Menu.
1.2. Setting up the Sensors
1. From the Setup menu, use the p and q buttons to 
highlight SENSORS.
2. Press the u button to display the Sensors menu.
Fig. 26. Setup - Sensors - Number of Sensors.
1.2.1. Number of SENSORS
The value entered here determines the number of 
sensors displayed on the home screen.
NOTE: For applications that do not use Reset, only 
one sensor (Sensor A) is available for use.
1. From the Sensors menu, highlight  # SENSORS then 
press the u button to display the number of sensors.
2. Use the p and q buttons to enter the number of sen-
sors (1 or 2).
Default: 2
3. Press the u button to accept the value and display 
the SENSOR A selection.
Fig. 27. Setup - Sensors - Sensor A Menu.
1.2.2. SENSOR A
If you are implementing two-sensor reset control, Sensor A 
must always be the controlled temperature and Sensor B must 
always be the controlling temperature. For example, in a reset 
control based on outside temperature, Sensor A must be the 
inside sensor and Sensor B must be the outside sensor.
1. From the Sensors menu, highlight SENSOR A.
2. Press the u button to display the Sensor A selec-
tions.
The menu selections change depending on whether the 
sensor type is 1097  PTC (temperature) or 0-10V / 4-
20MA.
 SETUP
 
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24586
ENTER
NUMBER OF 
SENSORS
SETUP
 SENSORS
 
# SENSORS
SETUP
SENSORS
# SENSORS
2
M24587
SETUP
 SENSORS
 
SENSOR A
SETUP
SENSORS
SENSOR A
TYPE
UNITS
CALIBRATE
LABEL
EXIT
SETUP
SENSORS
SENSOR A
TYPE
UNITS
MIN VAL
MAX VAL
CALIBRATE
LABEL
EXIT
SENSOR A
TYPE = PT1000
SENSOR A
TYPE = 0-5V, 0-10V,
OR 4-20MA
M24588A