Honeywell Home Theater Server T755U Manual De Usuario

Descargar
Página de 40
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
38
SUMMARY MENU
The Summary menu provides the ability to view the 
schedule (E1 and E2 times) for each relay for each day of 
the week.
NOTE: Scheduling must be enabled for the 
Summary menu to display. Enabling the 
schedule is determined in the Setup process 
for the Output Options (see page 22).
Fig. 86. Summary Example - Monday Settings.
For each relay, the Summary display indicates the time 
and temperature (in parenthesis) for each of the two 
scheduled events E1 and E2.
1. Press the MENU button to view the menu.
2. Use the p and q buttons to highlight SUMMARY.
3. Press the u button to display the Summary settings.
4. Use the u button to scroll forward through each day 
of the week (Monday, Tuesday, Wednesday, 
Thursday, Friday, Saturday, and Sunday).
5. While viewing a specific day, use the p and q 
buttons to cycle through the individual relay 
schedules for that day.
When finished, press the 
HOME button to return to the 
home display screen.
If programmed for Reset control, the Summary setpoints 
display as “RES” instead of a temperature value. For 
example, the display would show:
MONDAY
STAGES
E1: 06:00AM (RES)
- indicating Reset
E2: 06:00PM (05)
- setback/offset degrees
TROUBLESHOOTING
Power Loss
The date and time settings are retained for 24 hours after 
a power outage. After a power loss of more than 24 hours, 
the date and time settings may need to be reentered. All 
other settings are stored permanently.
Errors and Diagnostics
The controller provides an error message and diagnostic 
status as described below.
Error Message
There is a two-character error code that displays in 
response to controller software problems:
EE
EEPROM Failure— The values read back from 
the EEPROM are not the same as written into the 
EEPROM. This error cannot be field repaired. Replace 
the device.
Diagnostic Messages
There are two diagnostic messages that can display in 
response to sensor problems. The diagnostic codes that 
can flash on the display are:
– –
Sensor Open or Shorted — Two dashes display
when a sensor (typically temperature) is open or 
shorted. An open circuit is considered anything 
greater than 1570 ohms (greater than 300F), shorted 
anything less than 770 ohms (less than -73F). Which-
ever stages are operating with this sensor cease to 
control (meaning relays go to OFF and proportional 
outputs go to zero percent).
This message can also mean that the sensor is pro-
grammed, but not physically connected.
-60°F or 270°F (-51°C or 132°C) Blinking
Temperature Out of Range — The temperature 
display blinks when the sensed temperature range is 
outside of the display range, below -60°F (-51°C) or 
above 270°F (132°C). The displayed value remains at 
that displayed limit and control continues. Controller 
continues to function unless an open or shorted state 
is detected.
Blinking relay status
Relay Minimum Off Time is Active — On the home 
screen, each relay’s indicator (¢) blinks while the 
relay’s minimum off time is active.
SPECIFICATIONS
Power:  24, 120, or 240 Vac; 50/60 Hz 
A separate earth ground is required for any power 
source.
Power Consumption: 
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40°F to 125°F (-40°C to 52°C) @ 50 Hz
• -40°F to 140°F (-40°C to 60°C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90
• Floating
MENU
 
SUMMARY
MENU
SUMMARY
MONDAY
RELAY 1-2
E1: 06:00AM   (72)
E2: 06:00PM   (65)
M24629