Honeywell Galaxy 3-48C Instruccion De Instalación

Descargar
Página de 90
Galaxy 3 Series Installation Manual
A-4
Configuring as On-Line MAX
1.
Only if reprogramming an existing stand-alone MAX reader:
Put the MAX reader into the sleep mode (present the Void Master card then swipe twice with
the Program Master card — LEDs 2 – 5 switch on. Refer to the MAX Installation and
Operations Guide (L120)
.).
Remove the power from the MAX reader.
2.
Connect the AB line of the MAX reader to the AB line from the control panel (ensuring that a
daisy-chain connection is maintained and that the 680
Ω resistor is located in the last module on the
line). Connect 12 Vd.c. to the +VE and –VE terminal of the MAX reader.
3.
Ensure that the MAX mode is enabled (option 63.2.1 = OPTIONS.MAX.MAX Mode).
4.
Select option 63.2.2 = OPTIONS.MAX.MAX Address and press the ent key; the Galaxy
searches for the MAX with the highest address (the new MAX reader). The Galaxy 500 and 512
prompt for the AB line (1 – 4) that is to be searched; select the line and press the ent key.
Only if adding a new MAX reader: On locating the MAX address, the keypad prompts for the
OPERATING MODE of MAX to be assigned: select 0 = On-Line and press the ent key.
NOTE: If reprogramming an existing stand-alone reader, the system automatically selects the On-
Line operating mode
The MAX can then be readdressed. The keypad displays the current address of the MAX and the
range of valid addresses. Enter the new MAX address and press the ent key; the Galaxy then
reprograms the address of the MAX. The keypad indicates the old and new MAX addresses and
the status of the reprogramming.
NOTE: All new MAX readers default to address 7. It is recommended that when adding a reader,
it is addressed as the lowest available number on the line.
When the reprogramming is complete the MAX bleeps, the LEDs on the MAX switch off and the
keypad display returns to 2 = MAX Address.
NOTE: If the Galaxy has been warm-started with the MAX connected and the reader is re-
programmed with its existing address, then the LED does not switch off and engineering
mode does not have to be exited to configure the MAX into the system.
5.
Program the MAX Parameters. This option defines the operational features of the MAX reader.
1 = Descriptor: This option is used to assign a name of up to 12 characters to each of the MAX
modules.
2 = Open Timeout: This is the period, following the user card swipe, that the MAX relay is
activated allowing a door strike to be unlocked and the door to be opened without creating an
alarm. The MAX relay de-activates as soon as the door is closed or the Close Timeout occurs.
3 = Close Timeout: This is the period following the user card swipe that the door can remain open
when gaining access. If the door remains open longer than the period assigned to the Close
Timeout
, then an alarm occurs.
4 = Groups: Each MAX module can be assigned to selected groups; the MAX then responds only
to cards that have a group common to it.
Configuring On-Line MAX