Note: A battery system is recommended for highest reliability.  
Note: If a 120 VDC power supply is used rather than a battery, 
ensure an output capacitance of at least 12,000 µF, which 
can both sink and source electric current. See Power 
Supply Requirements (Table 1-2). 
Note: Use a separate conduit for the power wiring. This prevents 
noise pickup and transmission from ancillary equipment, 
which could cause instability in the actuator. 
Power Supply Requirements 
Table 1-2 below lists the power supply requirements for the HFG2.0. 
 
PARAMETER 
VALUE 
Voltage 
 Nominal 
 Range
 
 
120 VDC 
80 – 160 VDC 
Max. Ripple 
4 VAC RMS or 12 VAC p-p 
Current 
 Maximum 
 
Continuous , Typical  
 Transient, 
Typical
 
 
20 Amps 
<1 Amp 
+20 A  <60 ms 
+10 A  <600 ms 
-5 A  <100 ms 
*Output Capacitance 
12,000 µF  (typical) 
Table 1-2.  Power Supply Requirements 
*The output capacitance applies for non-battery power systems and assumes full-stroke step 
changes in actuator position at rated load. This value is typical. The actual value required is 
dependent on the user’s specific DC power system design, including: 
• 
Power sources used in the DC power system (their output impedance, transient response, 
rating, diode decoupling [if any], topology, etc.) 
• 
All electrical loads and components connected to each respective power bus branch 
• 
Switching relationships of these electrical loads and components to each other (for example, 
does a large motor and actuator turn off at about the same time, etc.) 
• 
Bus branch conductor length and arrangement (flat bus bars, round cables, twisted, etc.)