2.2  Electrical Description 
The electric actuator in the HFG2.0 incorporates digital motor control 
electronics (MCE). The MCE contain analog to digital converters, a digital 
signal processor (DSP), application specific integrated circuit (ASIC) and 
power supplies. Figure 2-1 shows the system block diagram. 
The MCE provides the interface for the user’s engine control system and 
power supply. The MCE incorporates analog and discrete inputs and 
outputs, and a serial interface. The MCE provides signal conditioning for 
all external analog and discrete I/O, as well as internal resolver and 
thermistor inputs. 
 Note: The MCE analog and discrete signal interfaces are 
electrically isolated. The serial communication interface is 
optically isolated 
  
The MCE internally interfaces with the brushless DC motor, resolver and 
thermistors. The MCE performs all necessary commutation, control and 
status monitoring for the HFG2.0. 
Power 
The HFG2.0 operates on an input voltage of 120 VDC (nominal) that is 
provided by the user via an integral four-wire power harness. Refer to 
Figure 1-10 or 1-11 for a typical connection. Refer to the General 
Specification Summary Table in Section 1.2 for load specification values. 
Control Signals 
The HFG2.0 accepts three two-wire external control signals via the 
integral 17-wire signal harness. Refer to Figures 1-13 and 1-15 for typical 
connections. Refer to the General Specification Summary Table in 
Section 1.2 for signal specification values. 
RUN Command 
The user-provided RUN command is a discrete input. The RUN 
command must be ON to enable the HFG2.0 to perform the homing 
sequence after resetting or powering up. The RUN command also 
enables the HFG2.0 to track the DEMAND signal. The valve will move to 
the Stop Position if the RUN command is set to OFF or lost.  
RESET Command 
The RESET command is a user-provided discrete input to the HFG2.0. 
This command causes the HFG2.0 to reset all internal position indicators, 
reload all set-up parameters, and to then move the valve through its initial 
homing sequence again. (The RUN command must be set to ON before 
the homing sequence can begin.) RUN and DEMAND inputs are ignored