3  OPERATING THE HFG2.0 
This section refers to the position of the actuator when describing 
operation of the HFG2.0 valve. The end of the actuator extension rod is 
connected to the poppet assembly of the valve. The linear motion of the 
actuator, both extension and retraction, is directly translated to the poppet 
assembly. The position of the actuator correlates directly to the position of 
the valve poppets relative to the orifices. The Home position of the 
actuator is the CLOSED position (zero position) of the valve. 
3.1  Powering Up 
When 120 VDC is applied, the firmware program in the HFG2.0 will clear 
all system registers, retrieve all necessary operating parameters from the 
electrically erasable programmable read only memory (EEPROM), and 
perform an internal status check. This will also happen after a RESET 
command has been received. See the flow chart in Figure 3-1 for an 
overview of this process. 
Note: If the HFG2.0 receives a SET-UP command from the 
ActWiz software via the RS232 interface after these steps, 
the system will transition to the Set-Up state.  This state 
allows the user to change the Set-Up parameters and to 
download the fault file.  See Section 3.8 for details. 
 
CAUTION 
Always remove the RUN command during power up. If a RUN 
command is given during the Set-Up parameter download phase of 
power-up, the valve will not respond until the download is complete 
and the Home position has been established. 
3.2  Finding Home Position 
When the program is complete with a status check, it waits for the RUN 
command. 
When the status check and other steps in the Power-Up/Reset process 
are complete, the HFG2.0 will wait until it receives the RUN command. At 
 
CH. 3: OPERATING THE HFG2.0 
39