44 HFG2.0 
USER 
GUIDE
 
A non-linear interpolation table can be created to define positioning at 16 
discrete current levels in the DEMAND signal range, but only during Set 
Up using the ActWiz Software. See the Section 3.8 for additional details 
about Set Up parameters. 
 
 
Figure 3-3.  Dead Band of Actuator, Position vs. DEMAND Curve 
3.6  Resetting the Actuator 
To reset the HFG2.0, +24 VDC must be applied across the RESET wires 
for at least 0.5 seconds. The leading edge of the RESET command 
causes the HFG2.0 to stop all other operations, but the actual resetting of 
the HFG2.0 does not begin until RESET is returned to its OFF state. The 
RESET command causes the HFG2.0 to reset all internal position 
indicators, reload all Set-Up parameters, and check the health of the 
electronics. See the flow chart in Figure 3-1 for an illustration of this. The 
HFG2.0 is now in the Power Up / Reset state. 
Once the RUN command is detected as ON, the actuator will then move 
through its initial homing sequence again. RUN and DEMAND inputs are 
ignored during the RESET command. 
If FAULT alarm is detected, toggling the RESET command will clear the 
FAULT alarm, but it will NOT clear the fault file.