Fault Type 
Persist Time 
Fault Action 
Motor 
10 Sec 
 
1 Sec 
 
Motor temp > 130° C, Fault. 
. If fault exists and 
Motor temp > 135° C for 10 Sec, shutdown. 
 
 
Motor temp > 130° C, Fault  
. If fault exists and Motor 
temp > 130° C for 60 Sec, shutdown. 
 
 
Electronics 
10 Sec 
 
 
1 Sec 
 
Electronics temp > 110° C, Fault. 
 
 
If fault exists and Electronics temp > 115° C for 10 Sec, 
shutdown. 
 
 
Electronics temp > 110° C, Fault. 
 
 
If fault exists and Electronics temp > 100° C for 15 Sec, 
shutdown. 
 
 
Table 3-4.  Fault Configuration For OVERTEMP Alarm  
 
Automatic Shutdown Feature 
The HFG2.0 has a self-protective shutdown feature. The HFG2.0 will 
shutdown if: 
•  Any two motor winding temperatures exceed 135 °C for ten (10) 
seconds 
 or more (130 
°C for 60 seconds   ) 
•  The electronics temperature exceeds 115 °C for 10 seconds  or 
more (100 
°C for 15 seconds  ) 
 
Note: The POSITION and MOTOR CURRENT feedback signals 
will both be set to 0 mA when the current to the actuator 
motor is removed. 
 
WARNING 
Property Damage and Injury Hazard – If the motor windings exceed 
135
° C 
 (130
°C  ) or the electronics exceed 115° C   
(100
° C  ), the MCE will shut down power to the motor and 
electronics thereby allowing the actuator to move with load. When 
power is removed, the return spring causes the poppets to return to 
the soft seats, thereby closing the valve. Touching the HFG2.0 may 
result in serious burn injury 
 
CH. 3: OPERATING THE HFG2.0 
49