controL oPtIons 
Basic bimetal thermostats with mercury switches or fully programmable electronic thermostats are available as 
part of your IGX-HV system. Match your heating, cooling, staging, and operational requirements to the appropriate 
thermostat.
HV2: 30%-75% Minimum outdoor air
The HV2 option is required when the minimum outdoor air volume 
exceeds 30% of the total supply air volume. With higher outdoor air 
volumes, mixed air temperatures 
can vary greatly. Accordingly, 
2-stage heating and/or cooling is 
recommended.
 Also, an airstream 
override thermostat is standard 
with HV2 to prevent cold air 
discharge (below 55˚ F) when the 
thermostat is satisfied. (electronic 
modulation is optional).
tc1: 1-stage Heating / cooling
TC1 is a coiled bimetal thermostat 
used for single-stage heating, cooling 
or heating-cooling systems.
tc2: 2-stage Heating
TC2 is a coiled bimetal 
thermostat used for 2-stage 
heating systems.
tc4: Programmable
TC4 has full seven-day program 
capability. The thermostat can 
be set for four times and eight 
temperature settings each day of 
the week. It can control up to two 
stages of heating and two stages 
of cooling.
tc5: deluxe Programmable
TC5 has full seven-day program 
capability. The thermostat can 
be set for two occupied and two 
unoccupied times with adjustable 
temperature settings for each day 
of the week. It can control up to 
three stages of heating and two 
stages of cooling. The Intelligent Fan™ feature energizes the 
fan continuously during occupied mode and intermittently 
with a call for heating or cooling in unoccupied mode. 
tc3: 2-stage Heating / 2-stage cooling
TC3 is a coiled bimetal 
thermostat used for 2-stage 
heating, cooling or heating-
cooling systems. It includes 
an adjustable heat anticipator, 
stops, and a locking cover.
Three heating and ventilating options are available to provide proper tempering and fulfill varying requirements for 
fresh outdoor air. In all cases, heating and cooling functions are controlled by a Greenheck room thermostat or a 
DDC system (by others).
HV1: 0%-30% Minimum outdoor air
HV1 is the most common among 
heating and ventilating units, allowing 
you to set the minimum outdoor air 
volume between 0 and 30% of the total 
supply air volume. With the relatively 
low percentage of outdoor air, mixed 
air temperatures are mild and stable. 
1-stage heating and/or cooling is 
recommended.
 (2-stage or electronic 
modulation is optional).
HV3: 100% return air
The HV3 option is available when no 
outdoor air is needed. With relatively 
stable return air conditions, 1-stage 
heating and/or cooling is strongly 
recommended.
 (2-stage or electronic 
modulation is optional).
Supply
Return Air
70% - 100%
Outdoor Air
0% - 30%
Supply
Return Air
25% - 100%
Outdoor Air
30% - 75%
Supply
Return Air
100%
Supply
Return Air
70% - 100%
Outdoor Air
0% - 30%
Supply
Return Air
25% - 100%
Outdoor Air
30% - 75%
Supply
Return Air
100%
Supply
Return Air
70% - 100%
Outdoor Air
0% - 30%
Supply
Return Air
25% - 100%
Outdoor Air
30% - 75%
Supply
Return Air
100%
Heating and Ventilating control
thermostat options