General Information
D-011-0152
11
Humidity Sensors
Table 6 lists the humidity sensors available for use with the EA800 Alarm System.
4-20mA Sensors
Theory of Operation
Industry standard 4-20mA sensors can be used with the EA800. However, it is important to verify that this type of 
sensor will operate properly over the entire output range.
Figure 6 shows an example of the loop circuit for a 4-20mA sensor whose minimum operating voltage is 8V or less 
when connected to an EA800 base unit that is powered with 12VDC.
Figure 6  I4-20mA Sensor Wiring Diagram - EA800 Aux Power Supply
Figure 7 shows an example of the loop circuit for a 4-20mA sensor whose minimum operating voltage is greater 
than 8V when connected to an EA800 base unit that is powered with 12VDC.
Figure 7  4-20mA Sensor Wiring Diagram - External Power Supply
Table 6
EA800 Compatible Humidity Sensors
Sensor
Part Number
Description
Operating Range/Parameters
HA-III+
PN M-001-0091
Humidity monitoring module
5% to 95% rh 
(non-condensing)
Wireless 
Humidity
PN M-001-0126
Wireless humidity monitoring 
module
5% to 95% rh 
(non-condensing)
+
DC
+
-
4.0V
200O
Aux Power
J5
+
(-)
+
(-)
Input N
J6
+
-
Vsensor
4-20mA 
Transmitter
EA800
Max Load of 
200O includes 
1000' of 22 AWG 
(2 conductor) 
wire connecting 
the EA800 to the 
4-20mA sensor
If Vsensor = 8V and Aux Power = 12V
+
DC
External 
Supply
+
-
4.0V
200O
Aux Power
J5
+
(-)
+
(-)
Input N
J6
+
-
Vsensor
4-20mA 
Transmitter
EA800
Max Load of 
200O includes 
1000' of 22 AWG 
(2 conductor) 
wire connecting 
the EA800 to the 
4-20mA sensor
If Vsensor > 8V and Aux Power = 12V