Install the Wired Sensors
2.
Mount the mounting plate as follows:
Mounting to 3-gang enclosure: Use four (4) machine screws to secure the mounting plate to the mating holes in 
the 3-gang enclosure. 
Mounting to drywall surface: Place the mounting plate in mounting position. Mark the four mounting hole 
locations. Install drywall anchors and secure the mounting plate to the anchors.
Note:
If wall-mounted, prepare a wiring access hole at this time. All wiring must pass through the opening in the 
center of mounting plate.
Install the Wired Sensors
Install the wired sensors in accordance with the instructions provided with the wired sensors.
1.
Mount each wired sensor in its designated location.
2.
Label each sensor's wires for easy identification.
3.
Route the wires from the sensor to the base unit and dress the wires as required by local code. It is important 
to ensure that the wires are protected along their entire length, are not stressed at any point, and are 
adequately supported along their entire length.
4.
Pass the wires through the mounted EA800 rear panel.
EA800 Base Unit Power Connections
Note:
Do not apply power to the base unit until you are ready to begin sensor programming. The base unit has 
a 30-minute timer that starts when the unit is first powered up. If at least one sensor is not added and pro-
grammed within the 30-minute time period, an alarm will occur.
1.
Using a terminal block adapter, connect power supply + and - leads to POWER IN (+) and (-) on J5. Observe 
proper polarity. If using a transformer, ensure that the transformer is an isolated power supply.
2.
If Aux Power Out is to be used, connect + and - leads to AUX POWER OUT (+) and (-) on J5 using a terminal 
block adapter.
Install the Wireless Sensors
CAUTION
!
Do not connect or disconnect power, sensor, or alarm wiring while power is applied. 
Connecting and disconnecting the EA800 base unit with power connected may damage the 
base unit or result in improper or unreliable operation.
CAUTION
!
Connection of unsuitable loads to this connection may damage the power supply and 
EA800 base unit, or result in improper or unreliable operation.
CAUTION
!
If the EA800 base unit will be connected to a remote alarm panel, do not connect 
the base unit to the alarm panel until after sensor connection and configuration 
is complete. Connecting the remote alarm panel before configuring the EA800 
sensors will result in false alarms at the remote panel.