Operation
This chapter provides instructions for doing the following:
Monitoring Environmental Conditions
The current environmental conditions measured by each sensor connected to the EA800 base unit are shown on 
the home screen. Depending on the current sensor status the home screen may be one of the following screens:
MONITORING screen: This screen is shown when there are no active alarms or pending alarms. This screen 
displays the current readings from all programmed sensors as shown in the example below.
Note: Dashes indicate that a sensor has not been programmed yet. 
MONITORING screen with pending alarm. A pending alarm indicates that 
a sensor has exceeded the low or high limits but that the condition has 
not exceeded the programmed delay (0 to 120 minutes). When an 
alarm is pending, the sensor’s reading is displayed in reverse text as 
shown in the example for wired sensor 2.
If conditions in the sensor’s area return to the non-alarm state within 
the alarm delay time, the text returns to normal. If conditions remain 
outside the programmed sensor alarm limits for longer than the delay 
time, the screen changes to the ACTIVE ALARMS screen below.
.
ACTIVE ALARMS Screen: This screen is displayed when conditions 
monitored by any programmed sensor exceed one of its programmed 
limits for longer than the programmed delay period. Only the active 
alarm(s) is displayed as shown in the example below. See “Viewing 
Active Alarms” on page 50 for
 the procedure to access alarm 
information
This column shows 
environmental readings 
for wireless sensors 5-8.
This column shows 
environmental readings 
for wired sensors 1-4.
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Current Date
Current Time
Sensor 5
Sensor 6
Sensor 7 (not installed)
Sensor 8 (not installed)
Pending alarm