Enviro EA800 Manual De Usuario

Descargar
Página de 98
74
D-011-0152
Accessories
Accessories
Accessories available for use with the EA800 Environmental Alarm System are listed below.
Wired Water Presence Sensor:
2-wire; maximum 304 m (1000 ft.) cabling length
Wired 4-20mA Sensor
EA800 load (160 Ohms maximum)
Relay Outputs
(9) Form C with 3-terminal NC/COM/NO connections.
Note: There are 8 primary relays (1 dedicated for each sensor) and 
1 auxiliary relay.
Relay Contact Ratings
Max 30VDC @ 1 amp resistive.
Not for use with AC power.
Relay Logic
Each relay is user configurable.
Display
128x64 graphic LCD, with blue backlight
Device Environmental Operating Range:
Humidity:
5 to 95% RH, non-condensing
Temperature, Operating:
0°C to 50°C (32° F to 122° F). Not for installation inside coolers or freezers.
Ambient Environmental Quality: Indoor use intended, non-corrosive environment
Conformity Certifications
FCC Part 15, Subpart C, Class B
ICES-003, Issue 3; 1997
NRTL CUE certification mark
Warranty
Two (2) Year Limited Warranty. See Warranty and Service Information.
Notes:
1. Where required, this equipment is to be isolated from the mains supply by a limited power source as specified 
in EN60950.
2. All terminals must be connected to a Class 2 Power Limited Circuit complying with the National Electric Code 
NFPA 70, Article 725.
3. See “Specifications” on page 46 for power supply requirements.
Table 15
Accessories
Item (Winland Part Number)
Description
BZ-3: Audible alarm module 
(PN 1183)
Buzzer for connection to auxiliary relay output that provides audible alarm 
indication.
Power supply (transformer)
(PN L-020-0085)
Regulated 110 VAC-to-12 VDC @ >500 mA (minimum) transformer suitable for 
use with EA800.
Note: Power supply must be a limited power source per notes 1 and 2 in 
Table 14.
Table 14
Specifications — continued
Item
Specification