Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Operation
28
3.6.1 Humidification
Infrared Humidifier
There are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode 
of each is similar, however, some of the variables or timings differ.
Infrared humidifiers are started at 100% humidification request, and stopped at 0%. Infrared humid-
ifiers cannot be driven in proportional mode.
An autoflush system automatically controls a water makeup valve to maintain proper levels in the 
infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours 
have elapsed since the last time the humidifier was on, then the humidifier is not turned on until the 
valve completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds for a small pan 
and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4-1/2 minutes 
for a small pan or 7-1/2 minutes for a large pan. Pan size is selected based on unit specifications and 
is preset at the factory.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-
odically to add water to the pan (about 45 seconds every 7 minutes of humidifier operation for a small 
pan, or 80 seconds every 10 minutes of operation for a large pan). This adds enough water to the pan 
to cause about a third of the total water used to be flushed out of the overflow standpipe located in the 
humidifier pan. This action helps to remove solids from the pan. The flush rate is adjustable from 
110% to 500% in 10% intervals. Default is 150%. If the water quality is poor, it may be desirable to 
increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is 
low, the flush rate adjustment can be increased so that sufficient water level is maintained during 
humidification. The flush rate parameter, Infrared Flush Rate (Service Menu, Options Setup), is 
adjustable from 110%-500%.
External Humidifier Control—Optional
A factory-supplied option may be provided to allow a start-stop command to be sent to the control of a 
remote-mounted humidifier.
Table 5
Parameters for infrared humidifier control
Parameter
IFS Default
IFL Default
Humidity in Last xx Hours
15 hours
15 hours
Prefill Time
30 seconds
60 seconds
Fill Time
4 minutes
7 minutes
Humidifier On Time
8 or 10 minutes
10 minutes
Flush Rate
150%