Operation
33
3.7.5 User Inputs / Customer Inputs
The user can connect and specify up to four inputs depending on unit configuration. The user 
inputs/customer inputs are digital inputs that influence the operating mode of the unit depending on 
the selection. The customer input configuration settings are in the Service menu under Set Alarms, 
Screen 2 of 7. The choices for the customer inputs are shown in Table 7 along with their associated 
reaction. A terminal strip is provided in the cooling unit to connect your contact closure to. You have 
the ability to set the control to react on an open or closed contact.
NOTE
To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event 
Table 7
Customer inputs
Setting
Reaction
Smoke
Event Only
Water Alarm
Event Only
C PMP Alarm
Event Only
Flow Alarm
Event Only
Stdby G Pmp
Event Only
Stdby Unit
Event Only
C-Input 1
Event Only
C-Input 2
Event Only
C-Input 3
Event Only
C-Input 4
Event Only
Rht Lockout
Event + Electrical Heaters Disabled
Hum Lockout
Event + Humidifier Disabled
Rht+Hum Lock
Event + Electrical Heaters and Humidifier Disabled
Comp Lockout
Event + Compressor(s) Disabled w/o Pump Down
Call Service
Event Only
High Temp
Event Only
Air Loss
Event Only
FC Lockout
Event + Free Cooling Disabled
Heater Alarm
Event + Heaters Off (PeX Only)
Flow AL SD
Event + Shut Down the Unit
Flow AL LC
Event + Lockout Compressors, No Pump Down (enabled only if at 
least one compressor is on; auto-reset depends on input status)
Comp Lock PD
Event + Compressor(s) Disabled w/ Pump Down
Enable FC
Forces Free Cooling to On
HTRJ VFD
Activates the HEAT REJ VFD ALARM; no other function
HTRJ TVSS
Activates the HEAT REJ TVSS ALARM; no other function