Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Service Menu Parameters
56
8.0
S
ERVICE
 M
ENU
 P
ARAMETERS
Service menus allow customized settings for site operations. The password for service menu parame-
ters is 5010.
The iCOM control firmware is being updated constantly. As a result, the Service menu parameter 
tables shown in this manual may be slightly different than what is shown on your cooling unit's dis-
play. Please check 
 for the latest iCOM User manual updates.
Table 23
Setpoints parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 5
Password
PASSWORD
W
-
Temperature Setpoint
TEMP SET
W
41-104°F (5-40°C)
Control Type
CTRL TYP
W
Proportional, PI, PID, Intelligent
Temperature Proportional Band
TEMP PB
W
2-54°F (1-30°C) autoset
Temperature Integration Time
TEMP INT
W
0-15 min, autoset
Temperature Derivative Time
TEMP DER
W
0-900 sec
AutoSet Enable
AUTOSET
W
No, Yes
Temperature DeadBand
TEMP DB
W
0-36°F (0-20°C)
Second Setpoint
2ND SETP
W
41-104°F (5-40°C)
Backup Temperature Setpoint
BACK TSP
W
41-104°F (5-40°C)
Page 2 of 5
Password
PASSWORD
W
-
Humidity Setpoint
HUM SET
W
20-80%
Humidity Control Type
HUM CTRL
W
Relative, Compensated, Predictive
Humidity Proportional Band
HUM PB
W
1-20%
Humidity Integration Time
HUM INT
W
0-15 min
Humidity Deadband
HUM DB
W
0-50%
Dehum/Heat Low Limit 1
LO LIM 1
W
-9.9°F to -2.0°F
Dehum/Heat Low Limit 2
LO LIM 2
W
-9.9°F to -2.0°F
internal variable Low Limit 1 reset
-10.0°F / -2.0°F
-5.5K / -1.1K
internal variable Low Limit 1 reset
-10.0°F / -2.0°F
-5.5K / -1.1K
Page 3 of 5
Password
PASSWORD
W
-
Supply Limit
SUP LIM
W
Enabled, Disabled
Supply Limit Temp Value
SUP TEMP
W
41-77°F (5-25°C)
DT between Room / FC Type
FC TYPE
W
No, Contact, Value
DT between Room Air/ FC Fluid
FC DT
W
0-36°F (-18 - 2 °C)
Minimum CW Temp
MIN CW
W
No, Yes
Minimum CW Temp Value
MIN CW
W
32-68°F (0-20°C)
VSD Fanspeed
FANSPEED
W
Auto / Manual
°C / °F
% RH
SET