Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 84
Service Menu Parameters
69
TYPE
-
-
-
COMP 1 SHORT CYCLE
SC1
W
MSG, WRN, ALM
COMP 2 SHORT CYCLE
SC2
W
MSG, WRN, ALM
NO POWER
NOP
W
MSG, WRN, ALM
CONDENSER 1 FAILURE
CN1
W
MSG, WRN, ALM
CONDENSER 2 FAILURE
CN2
W
MSG, WRN, ALM
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Table 29
Sensor calibration / setup parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
Page 1 of 3
Password
PASSWORD
W
-
Return Temperature
RTN TEMP
W
±18°F (±9.9°C)
Calibrated Return Temperature
CAL TEMP
R
32-122°F (0-50°C)
Return Humidity
RTN HUM
W
±9.9%
Calibrated Return Humidity
CAL HUM
R
20-80%
Digiscroll 1 NTC
DS1 NTC
W
±18°F (±9.9°C)
Calibrated Digiscroll 1 NTC
CAL DS1
R
84-313°F (29-156°C)
Digiscroll 2 NTC
DS2 NTC
W
±18°F (±9.9°C)
Calibrated Digiscroll 2 NTC
CAL DS2
R
84-313°F (29-156°C)
Page 2 of 3
Password
PASSWORD
W
-
Temperature Sensor A
TEMP A
W
±18°F (±9.9°C)
Calibrated Temperature Sensor A
CAL A
R
32-122°F (0-50°C)
Humidity Sensor A
HUM A
W
±9.9%
Calibrated Humidity Sensor A
CAL A
R
20-80%
Temperature Sensor B
TEMP B
W
±18°F (±9.9°C)
Calibrated Temperature Sensor B
CAL B
R
32-122°F (0-50°C)
Humidity Sensor B
HUM B
W
±9.9%
Calibrated Humidity Sensor B
CAL B
R
20-80%
Page 3 of 3
Password
PASSWORD
W
-
Table 28
Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display
Small Display
SET
ALARMS
+ / -