NOTE: Install a Cyclades PM IPDU zero U model in a location where there is an adjacent and accessible wall 
socket outlet.
To mount the Cyclades PM8i IPDU, PM10 IPDU or PM10i IPDU:
1.
Locate the appropriate sets of holes on the PM IPDU.
Figure 2.2: Rack Mounting Holes on the PM8i IPDU, PM10 IPDU and PM10i IPDU
2.
Connect the two supplied brackets to the PM IPDU, connecting one bracket to each side of 
the box.
3.
For each bracket, insert a screw through each of the three holes on the bracket into the 
appropriate holes at either end of the PM IPDU. 
The following figure shows the bracket flanges on the front of the PM IPDU after the brackets 
are installed.
Figure 2.3: PM10 IPDU with Mounting Brackets Installed
4.
Use a Phillips screwdriver to tighten the screws.
5.
Use the mounting hardware recommended for your rack to mount the PM IPDU on a rack as 
illustrated in the following graphic.
Reliable Grounding
Reliable grounding of rack-mounted equipment should be maintained. 
Particular attention should be given to supply connections other than direct 
connections to the branch circuit, such as power strips or extension cords.
Table 2.6: PM IPDU Optimum Installation Environment (Continued)
Environment Factor
Recommendation
Side of the PM IPDU
Holes for Front Mounting
Holes for Back Mounting
Brackets