Carrier Access Network Device Axxius 800 Manual De Usuario

Descargar
Página de 568
Axxius 800 - Release 2.2
3-7
 
Electrical Installation and Cabling
Chassis Connections
Power Connections
There are three power supplies available with the Axxius 800; 24 VDC and 48 VDC 
and 48 VDC NI, all use this connector. The Axxius 800 supports a redundant power 
system, therefore there is INPUT (power) P1 and P2. 
Input Power 
A separate 
fuse should be used for each DC input
NOTE:  
If two power supplies are installed into the system they MUST be 
of the same type (24 VDC, 48 VDC or 48 VDC NI).
Wire each connector to a power source:
1. Ensure that no power is present on the two wires to be connected.
DANGER!   
P
OSSIBLE
 
SHOCK
 
HAZARD
 
EXISTS
PLEASE
 
FOLLOW
 
INSTRUCTIONS
 
CAREFULLY
.
2. Strip the two wires from the power source so that approximately 5/16 inch of 
bare wire is exposed. 16
 
or
 
18
 
AWG
 
insulated
 
copper
 
wire
 
is recommended 
for power
 
connections.
3. Insert the Battery Return and DC wires into the appropriate square holes, one 
at a time.
4. Tighten screws to clamp wires.
Power Supply
Rated Amperage 
Recommended External 
Input Fuse
24 VDC
5 Amp 
7 Amp
48 VDC/48 VDC NI
2.5 Amp
3.5 Amp