52C
SERIES
2
GENERAL
Thank you for choosing Carrier! You can feel confident 
in your selection because the same pride in craftsman-
ship and engineering knowledge that goes into Carrier 
equipment at the Astrodome in Texas, the Sistine 
Chapel in Rome, the US Capitol Hall of Congress, and 
thousands of other installations worldwide has gone 
into the construction of this unit.
The Carrier package terminal air conditioners and 
heat pumps provide a high standard of quality in per-
formance, workmanship, durability and appearance as 
they heat and cool the occupied air space year round.
This manual provides information for ease of installa-
tion, operation and maintenance of the 52C unit. The 
following units are covered in this manual (see
Figure 1 for additional unit information):
52CE 60 Hz cooling with electric heat units
52CQ 60 Hz cooling, electric heat, and heat pump units
All models are designed for through-the-wall instal-
lation. Separate installation instructions are included 
with all accessory components. See Accessories section 
on page 14 for complete listing of accessories.
UNIT INSPECTION
Examine unit for damage incurred during shipment. 
File a claim immediately with the transit company if 
damage is found.
The data information plate (Figure 1) lists the model 
number, voltage ranges, and other important electrical 
information about this product. Reading and under-
standing this material is important for proper use of 
this unit. To access the information plate, the front 
panel must be removed; see Figure 2.
FRONT PANEL
To remove the front panel:
1. Grasp panel firmly near bottom of both sides.
2. Pull panel forward then upward to release mag-
netic latches and partition hooks.
NOTE: Front panel may be secured to chassis with
2 screws located behind indoor air inlet filters. In order 
to remove these screws, the filters must be removed 
first. Refer to page 10 in this manual for instructions on 
removing indoor air inlet filters.
Using Figures 1 and 3 as reference, verify that the 
packaged terminal product ordered will operate prop-
erly in your facility. If you do not understand the in-
formation given or have questions about the product, 
please call your local dealer or distributor.
Replacement Package Terminal Air Conditioner, 
CLASSIFIED BY UNDERWRITERS LABORATO-
RIES INC., AS TO ELECTRIC SHOCK, FIRE AND 
CASUALTY HAZARDS ONLY. FOR FIELD INSTAL-
LATION WITH EXISTING WALL SLEEVES, OUT-
DOOR LOUVERS, AND INDOOR PANELS AS 
SPECIFIED ON THE PRODUCT.
IMPORTANT: The front panel has to be off the unit 
to complete future checks and installation proce-
dures. Do not reinstall front panel at this time
CANADIAN INSTALLATION
SERIAL     0201X11520
DATE OF MFG.       01/12/2001
VOLT RANGE        187-253
VOLTS       230/208
PH     1
MODEL       52CQA312301AA
HZ
60
MIN CKT AMPACITY            17.9
R-22 OZ      34
DESIGN PSIG 350 HIGH SIDE, 150 LOW SIDE
COOLING
HEATING
BTU/HR       12,00/11,900
AMPS        5.8/6.2
WATTS    1333/1311
EER          10.1/10.1
MOTOR
FAN
COMP
HP
FLA
RLA
LRA
70
33.2
1.0/0.8
1/8
BTU/HR          10,800/10,700
AMPS         15.8/14.5
WATTS       3600/3025
COP             3.0/3.0
HEATER
BTU/HR
AMPS         14.8/13.7
WATTS      3400/2850
WATER
STEAM
20
20
20
USE
TIME DELAY FUSE
OR HACR TYPE
CIRCUIT BREAKER
AMP
AMP
AMP
MAX FUSE
MAX BREAKER
FIGURE 1 — SAMPLE DATA INFORMATION PLATE
FIGURE 2 — REMOVING FRONT PANEL