SECTION 8.  PROCESSING AND PROGRAM CONTROL EXAMPLES
8-6
situation, it is more likely that the pulse
counters would be used for 2 wind speeds.)  In
Program Table 1, the 2 normal pulse inputs are
read and the hourly totals output to Final
Storage with Instruction 72.
The rain gage is connected as diagrammed
below.  When the switch closes, 5 volts is
applied to port 8 which causes the subroutine to
be executed.
FIGURE 8.5-1.  Connections for Rain Gage
Input location Assignments:
10:Rain #1
(from Pulse count)
11:Rain #2
(from Pulse count)
12:Rain #3
(from subroutine 98 while
Output Flag is low)
13:Rain alt
(from subroutine 98 while
Output Flag is high)
*
1
Table 1 Programs 
01:
10
Sec. Execution Interval 
01:
P3
Pulse 
01:
2
Reps 
02:
1
Pulse Input Chan 
03:
2
Switch Closure 
04:
10
Loc [:Rain #1  ] 
05:
.254
Mult 
06:
0
Offset 
02:
P92
If time is 
01:
0
minutes into a 
02:
60
minute interval 
03:
10
Set high Flag 0 (output) 
03:
P77
Real Time 
01:
110
Day,Hour-Minute 
04:
P
72 Totalize 
01:
2
Reps 
02:
10
Loc Rain #1 
05:
P91
If Flag/Port 
01:
10
Do if flag 0 (output) is high 
02:
30
Then Do 
06:
P70
Sample 
01:
1
Reps 
02:
12
Loc Rain #3 
07:
P30
Z=F 
01:
0
02:
0
Exponent of 10 
03:
12
Z Loc [:Rain #3  ] 
08:
P86
Do 
01:
20
Set low Flag 0 (output) 
09:
P33
Z=X+Y 
01:
13
X Loc Rain alt
02:
12
Y Loc Rain #3 
03:
12
Z Loc [:Rain #3  ] 
10:
P30
Z=F 
01:
0
02:
0
Exponent of 10 
03:
13
Z Loc [:Rain alt ] 
11:
P95
End  
12:
P
End Table 1   
*
3
Table 3 Subroutines   
01:
P85
Beginning of Subroutine 
01:
98
Subroutine Number   
02:
P91
If Flag/Port 
01:
10
Do if flag 0 (output) is high 
02:
30
Then Do  
03:
P34
Z=X+F 
01:
13
X Loc Rain alt 
02:
0.254
03:
13
Z Loc [:Rain alt ] 
04:
P94
Else   
05:
P34
Z=X+F 
01:
12
X Loc Rain #3 
02:
.254
03:
12
Z Loc [:Rain #3  ] 
06:
P95
End  
07:
P22
Excitation with Delay 
01:
1
EX Chan 
02:
0
Delay w/EX (units=.01sec) 
03:
20
Delay after EX
(units=.01sec) 
04:
0
mV Excitation  
08:
P95
End   
09:
P
End Table 3