Connection and Wiring
5
AXB-REL8 Axcess Relay Controller
AXlink data and power connections
Connect the control system's AXlink connector to the AXlink connector on the rear panel of the 
AXB-REL8 for data and 12 VDC power as shown in FIG. 3.     
Wiring AXlink with optional 12 VDC power supply
Connect the control system's AXlink connector to the AXlink connector on the rear panel of the 
AXB-REL8 as shown in FIG. 4.      
Use a 12 VDC power supply when the distance between the control system and AXB-REL8 
exceeds the limits described in the Wiring Guidelines at 170 mA table on page 4, or the power 
supply current capacity cannot accommodate the 170 ma (max) draw of the AXB-REL8. Make sure 
to connect the GND and +12 VDC wire on the AXB-REL8 AXlink connector end. Do not connect 
the optional +12 VDC power supply wire to the control system's power supply side of the AXlink 
Checking the installation
After set-up is complete:
1.
Check continuity of relay wiring.
2.
Check cable numbers and wiring, interfaces and sources against supplied documentation.
3.
Install tab strips to jumper between shared commons and clip off excess tabs.
4.
Insert relay wiring terminals into AXB-REL8.
Relay connections
The relay specification is 1 A @ VAC or VDC. FIG. 5 on page 6 shows the relay wiring diagram 
for the AXB-REL8. The dotted lines are used to indicate commons. Install supplied tab strips to 
jumper between shared commons. Clip off excess tabs and bend strip up, away from other wiring.        
FIG. 3  AXlink wiring
FIG. 4  Wiring AXlink with Optional 12 VDC power supply 
PWR +
AXP/TX
AXM/RX
GND -
PWR +
AXP/TX
AXM/RX
GND -
AXB-REL8
Central Controller
PWR (+)
GND (-)
Local +12 VDC power supply
(coming from the PSN power supply)
PWR +
AXP/TX
AXM/RX
GND -
PWR +
AXP/TX
AXM/RX
GND -
AXB-REL8
Central Controller