AEG Portable Generator 2.33 2 Manual De Usuario

Descargar
Página de 80
25
4.2.4. locatioN
The security instructions indicate that it is necessary to leave a minimum of 25 cm 
around the equipment for ventilation (2 UPs devices in parallel operation should 
be set 50 cm apart from each other. see Fig.14 and 15.) nevertheless, we recom-
mend to leave another 75 cm additional space to facilitate maintenance of the 
equipment or technical service intervention in event of a breakdown.
The UPs may be put in any place as long as the safety instruction requirements are 
fulfiled and the weights are considered as indicated in table 5 and 6.
The UPs includes 2 leveling elements (PB) located near the front castors, which 
serve to immobilise the unit once it is in place.
Open the front door (PF) of the cabinet and proceed as follows:
•  By hand, loosen the leveling elements (PB) by turning them anti-clockwise until 
they touch the floor. Then, using a spanner, continue loosening until the castors 
are raised off the floor by a maximum 0.5 cm, ensuring that it is level.
•  Close the door (PF).
Fig.14:  Front view UPS location for single unit
Fig.15:  Top view UPS location for single unit