common ground is connected to pin 5. Furthermore, an input signal can be used 
to shut down the UPs (5 VDC – 12 VDC.)
PIn-OUT nO.
DesCrIPTIOn
n.C.-n.O. POsITIOn
1
shutdown signal +
-
2
shutdown signal –
-
3
Configurable
not connect
4
Discharge - Mains failure
n.C.
1
5
Common
-
6
equipment in Bypass
n.O.
2
7
low battery
n.O.
8
General alarm
n.O.
9
Discharge - Mains failure
n.O.
1
 n.C.: normally closed contact. On the alarm having activated the contact 
   is opened.
2
 n.O.: normally open contact. On the alarm having activated the contact 
  is closed.
4.3.6. com-iNtErFacE rs232 aNd rs485, coNNEctor (X31)
The serial communications interface operates over low voltage. To ensure safe and 
trouble-free communication, install at a safe distance from the power supply lines 
to the UPs. 
The X31 DB9-connector is used for communication to rs232 or rs485 standard 
connectors. Both standards cannot be used simultaneously.
Both channels are in use for connecting the UPs with any machine or devices that 
has this standard bus. The rs232 consists of the transmission of serial data, so it is 
possible to send a large amount of information through a communication cable of 
just 3 wires.
Table 2:  Alarms interface to relays connector DB9 (X32)
Fig.21:  Connector DB9 (X31) & (X32)