DMP Electronics XR2500F Manual De Usuario

Descargar
Página de 60
Digital Monitoring Products 
XR2500F Installation Guide
18
InstallatIon
Standby Battery Power Calculations
Standby Current
Alarm Current
736P POPIT Interface Module 
Radionics Popex, POPITs, OctoPOPITs 
Qty ______
Qty ______
x
x
25mA
___mA
______
______
Qty ______
Qty ______
x
x
25mA
___mA
______
______
710 Bus Splitter/Repeater Module
Qty ______
x
32mA ______
Qty ______
x
32mA ______
710F Fire Bus Splitter/Repeater Module
Qty ______
x
40mA ______
Qty ______
x
40mA ______
711 Zone Expansion Module 
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
11mA
1.6mA
______
______
Qty ______
Qty ______
x
x
11mA
*2mA
______
______
714 Zone Expansion Module 
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
7mA
1.6mA
______
______
Qty ______
Qty ______
x
x
7mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module 
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
20mA
1.6mA
______
______
Qty ______
Qty ______
x
x
20mA
*2mA
______
______
715 Zone Expansion Module 
Active Zones (EOL Installed) 
2-Wire Smokes
Qty ______
Qty ______
Qty ______
x
x
x
7mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules 
Active Zones (EOL Installed) 
2-Wire Smokes
Qty ______
Qty ______
Qty ______
x
x
x
20mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
20mA
*30mA
.1mA
______
______
______
716 Output Expansion Module 
Active Form C Relays
Qty ______
x
13mA ______
Qty ______
Qty ______
x
x
13mA
12mA
______
______
717 Graphic Annunciator Module 
Annunciator Outputs
Qty ______
x
10mA ______
Qty ______
Qty ______
x
x
10mA
1mA
______
______
521LX, 521LXT Smoke Detectors
Qty ______
x
8.8mA ______
Qty ______
x
*28mA ______
Aux. Powered Devices on Terminals 7 and 11 
Other than Keypads and LX-Bus Modules
______mA
______mA
This page only
 
Sub-Total Standby ______mA
Sub-Total Alarm ______mA
Sub-Totals from previous page
 
Sub-Total Standby ______mA
Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm
Total Standby ______mA
Total Alarm ______mA
 
Total Standby______mA x number of Standby Hours needed 
Total Alarm
______ =
______mA
Total
 
  _______mA-hours
+_______mA-hours
  _______mA-hours
X      .001 
= _______Amp-hrs 
Required