Delta Electronics DVPDNET-SL Manual De Usuario

Descargar
Página de 32
DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
26
editing area to 0. 
„ When M1 = On, DVPDNET-SL will send out request message. Write 0004Hex into Class 99 >> 
Instance 1 >> Attribue 2 of the target equipment (node address: 02). If the communication of 
explicit message is successful, the slave will return with a response message. 
„ When M1 = On, DVPDNET-SL will only send out request message once. If you would like it to 
send out request message again, you will have to change ReqID. 
„ When the writing is successfully done, the message responded from the target equipment will be 
stored in D6000 ~ D6003. 
7 Bit-Strobe 
Command 
7.1 Principle 
of 
Bit-Strobe 
Bit-strobe is one of the standard I/O transmission methors for DeviceNet. The length of command is fixed to 
8 bytes (i.e. 64 bits), and every bit corresponds to a slave. 
Corresponding nodes on the network 
PLC 
device 
b15 
b14 
b13 
… 
b1 
b0 
D6282 
Node 15 
Node 14 
Node 13 
… 
Node 1 
Node 0 
D6283 
Node 31 
Node 30 
Node 29 
… 
Node 17 
Node 16 
D6284 
Node 47 
Node 46 
Node 45 
… 
Node 33 
Node 32 
D6285 
  Node 63 
Node 62 
Node 61 
… 
Node 49 
Node 48 
When b0 of D6282 = 0, the node 0 equipment will be selected, and it will need to respond with a message to 
the master. When b0 and b1 of D6282 = 0, the node 0 and node 1 equipment will be selected, and they will beed 
to respond with a message to the master. 
b0
b1
b17
b15 b14
b30
b2
b18
b16
b31
D6283
Node 0
Node 1
Node 2
Node 14
D6282
 
In the bit-strobe mode, the master will not send control data to the slave node. However, when its 
corresponding bit is set to 0, the slave node will have to respond with I/O data to the master. When its 
corresponding bit is set to 1, the slave node will not have to respond with I/O data to the master.
 
Display of Node Status on Network 
8.1 
Display of Node Status in Scan List 
DVPDNET-SL does read-time monitoring to the nodes in the scan list and maps the status of every node to a 
bit. You can acquire the node status by monitoring D6032 ~ D6035. See the table below for the corresponding 
relation between PLC devices and the nodes on the network: