DeviceNet Network Scanner DVPDNET-SL
 
DVP-PLC Application Manual 
3
1 Introduction 
1.  To ensure correct installation and operation of DVPDNET-SL, please read this chapter carefully before using 
your DVPDNET-SL.   
2.  This chapter only provides introductory information on DVPDNET-SL. For more detailed information on 
DeviceNet protocol, please refer to relevant references or literatures. 
3.  DVPDNET-SL is a DeviceNet master module operating on the left side of DVP-SV series PLC MPU. When 
DVP-SV is connected to DeviceNet through DVPDNET-SL, DVPDNET-SL will serve as the data exchange 
interface between DVP-SV and other slaves on the bus. DVPDNET-SL is in charge of sending the data in 
DVP-SV to the slaves on the bus, and at the same time collecting the data returned from each slave and 
sending them back to DVP-SV. 
1.1 Features 
z  Supports Group 2 server device and Group 2 only server device. 
z  Supports explicit connection via predefined Master/Slave connection set. 
z  Supports DeviceNet Master mode and Slave mode. 
z  Supports EDS configuration in DeviceNet configuration tools. 
1.2 
Basic Functions of DVPDNET-SL 
DVPDNET-SL DeviceNet Network Scanner can be used both as a master or a slave in DeviceNet. When 
being used as a master, it supports the following functions: 
z  Client function of explicit message. 
z  All kinds of I/O connections established between the slave: polled, bit-strobed, change of state and 
cyclic. 
z  As the connection interface between DeviceNetBuilder configuration software and DeviceNet network. 
The configuration software is able to directly configure the network through DVPDNET-SL. 
z  Sending explicit messages for reading/writing the data in slave through PLC ladder diagrams.   
z  Automatically exchanging data with PLC MPU. The user needs only to edit the D register in the PLC 
without using FROM/TO instruction.
 
When connected to DVP-SV/DVP-EH2-L MPU,
 
registers after 
D6000 will be adopted temporarily. 
z  Offering 380-byte space for I/O input data and another 380 bytes for I/O output data. 
When being used as a slave, it supports the following functions: 
z  Explicit message serve and Group 2 only serve connection mode. 
z Polling 
z  Offering 256 bytes for input data and 256 bytes for output data in data exchange with master. 
z  Automatically exchanging data with PLC MPU. The user needs only to edit the D register in the PLC 
without using FROM/TO instruction.